Breakers, Relays and Disconnects Flashcards

1
Q

What are five basic categories of circuit interruption devices found in the power system?

A
Disconnect switches
Air break switches
Load break switches
Power fuses, and 
Circuit breakers
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of a Disconnect Switch?

A

The are unable to interrupt any current flow, and must only be operated when current flow is zero. Disconnect
switches are essential to personnel safety when performing maintenance work because they provide positive visual evidence that it is open.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of Air Break Switches?

A

They are normally used in high voltage systems, and can be used to interrupt the exciting currents of transformers or the moderate capacitive currents of unloaded transmission lines. They cannot interrupt normal load
currents. The name “air break” denotes that the operation of the switch and quenching of the arc are done in the open air.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the purpose of Load Break Switches?

A

They are used to stop and/or transfer current flow. Load pickup is not as severe as load interruption because the arc is reduced when the switch contacts are closed. Due to the potentially large current flows, the load break switch construction is more rugged, with additional components to prevent main contact damage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the purpose of Power Fuses?

A

Fuses disconnect the protected circuit from the power source. The disadvantage of this type of interrupter is that
replacement is required after each actuation (failure).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the purpose of Circuit Breakers?

A

They are used to connect or disconnect a power circuit to a power source and can perform the protective function of interrupting fault current of the power source.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are three common ways of classifying circuit interrupting devices?

A

By dielectric material, operating voltage range, and type of operating mechanism.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Describe the use of dielectric materials in circuit interrupters.

A

The purpose of a dielectric medium is to surround the breaker contacts and help cool and extinguish (quench)
the arc during operation. It insulates (prevents current flow) the space between the contacts when they are open. A number of different mediums for quenching an arc: ambient air, oil, high-pressure air, or special gases such as sulfur hexafluoride (SF6) are available.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Define dielectric strength.

A

It is the ability of a material to withstand voltages without conducting current.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Define Voltage Rating in terms of circuit breakers.

A

Three common voltage classifications are low (15kv). This voltage classification may not always be the rated voltage. For example, a breaker rated at 7.25 kV may be called a 6.9 kV breaker because that is the operating voltage of the system in which it is installed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Define Frame Rating in terms of circuit breakers.

A

The maximum continuous current ratings in amps of all parts except the overcurrent device. Some breakers have a mechanical interlock to prohibit insertion of a different rated breaker into a cabinet.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Define Continuous Current Rating in terms of circuit breakers.

A

A current value equal to or less than the frame rating. This value of current is the rating of the overcurrent device. It is possible to have a 600 amp frame circuit breaker that has a continuous current rating of only 40 amps.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Define Interrupting Rating in terms of circuit breakers.

A

The highest current at rated voltage the device can interrupt without external damage. Typical ratings range from 22,000 to 200,000 amps symmetrical. Interrupt ratings vary between manufacturer, voltage, frame rating of breaker, and whether high-fault protectors are installed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Define Time Delay Rating in terms of circuit breakers.

A

Circuit breakers, like fuses, are rated by the amount of time delay they provide. In circuit breakers, the ratings are: instantaneous, short time delay, and long time delay. The delay times of circuit breakers can be used to provide selective tripping. Selective tripping allows breakers to trip in sequence. Normally the breaker nearest the load should trip first.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Define Control Power in terms of circuit breakers.

A

If a circuit breaker can be electrically opened, closed, or has a motor to charge the closing springs, there will be a control power requirement. Often this control power
is further broken down into control and trip power. This separation allows the protective circuits to be fused differently than the control power circuits.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Define Main Stabs in terms of circuit breakers.

A

Plug-in connection points between the circuit breaker and switchgear cabinet. Circuit load current flows through them.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Define Auxiliary Stabs in terms of circuit breakers.

A

Plug-in connection points between the circuit breaker and switchgear cabinet. These stabs can be used for spring-charging motor, motor power, trip circuits, control circuits, instrumentation circuits, or any other electrical interface with the breaker.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Define Main Contacts in terms of circuit breakers.

A

These contacts are designed to carry the normal operating current.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Define Arcing Contacts in terms of circuit breakers.

A

Close first and open last during breaker operation. These contacts are designed and used as sacrificial elements so that only minimal damage to the main contacts occurs during breaker operation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What are the four general classifications of circuit breakers.

A
  1. Air Circuit Breakers (ACBs)
  2. Oil Circuit Breakers (OCBs)
  3. Vacuum Circuit Breakers (VCBs)
  4. Gas Circuit Breakers (GCBs)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Describe an Air Circuit Breaker.

A

They simply elongate the arc in air until it is extinguished. ACBs can be made to interrupt currents of 50,000 amps in AC circuits operating at up to 10,000 volts. The breakers typically have a piston that puffs air across the contacts as they operate. This puff of air assists in extinguishing the arc.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Describe an Oil Circuit Breaker.

A

These are breakers immersed in insulating oil. The oil vaporizes between the contacts to extinguish the arc.
OCBs can be made to interrupt currents up to 10,000 amps, in circuits operating at up to 500 kV.

23
Q

Describe a Vacuum Circuit Breaker.

A

These are breakers contained in a vacuum. The vacuum is maintained so that there is nothing to ionize to form an arc between the parting contacts.

24
Q

Describe a Gas Circuit Breaker.

A

These are breakers contained in a quenching gas. The quenching gas, typically sulfur hexafluoride (SF6), essentially prevents the formation of an arc due to its dielectric properties.

25
Q

Describe the system effects when control power is lost to one or more circuit breakers.

A
  1. Inability to trip the breaker remotely, automatically, or on a fault.
  2. Inability to remotely close breaker.
  3. Loss of remote and local indicating lights.
  4. Inability to electrically recharge closing springs
26
Q

State the purposes for racking out breakers.

A

It is a means of keeping equipment de-energized for

maintenance, to protect maintenance personnel and the equipment itself.

27
Q

Can a zero amp meter reading be used to indicate breaker position?

A

No. A zero ammeter reading is not positive indication of an open breaker, only that no load is being supplied. Load amps provide reliable indication if greater than zero, since load indicates the breaker is closed and loaded.

28
Q

Describe the circuit breaker effects when in the test position.

A

The main stabs are disconnected but the auxiliary stabs stay connected. The “Test” position allows cycling
of the breaker without load starting.

29
Q

Why are grounds installed during some breaker tagging evolutions?

A

This ensures the load side of the breaker remains at ground potential and no voltage or current is induced in the load side conductors.

30
Q

State the three conditions necessary to parallel power sources.

A
  1. Their terminal voltages must be equal.
  2. Their frequencies must be equal.
  3. Their output voltages must be in phase.
31
Q

Identify the effects of closing AC generator output breakers during paralleling operations with currents out of phase.

A

A mismatch in the phases will cause large opposing voltages to be developed. The worst case mismatch would be 180° out of phase, resulting in an opposing voltage between the two generators of twice the output voltage. This high voltage can cause damage to the generators and distribution system due to high currents.

32
Q

Identify the effects of closing AC generator output breakers during paralleling operations with differential frequencies.

A

If an incoming machine is paralleled at less than synchronous speed, even if it is in phase at that time, there will be a flow of energy from the system to the incoming machine to accelerate it to synchronous speed. This condition (“motoring” the generator) will result in very high current in the machine windings in an attempt to produce the necessary torque to accelerate the incoming machine. If the incoming machine is running faster than synchronous speed, and the breaker is closed, there will be a flow of energy from the machine to the system to slow the machine to synchronous speed. The amount of energy flow is proportional to the speed difference.

33
Q

Identify the effects of closing AC generator output breakers during paralleling operations with high voltage differential.

A

If voltages are not matched at the time the breaker is closed, there will be a VAR flow from the system to the incoming machine if the machine voltage is lower (leading power factor), or from the machine to the system if the machine voltage is higher (lagging power factor). Any power factor other than one leads to reactive power being generated. The reactive power increases the load on the generator.

34
Q

Identify the effects of closing AC generator output breakers during paralleling operations with a frequency relationship that results in reverse power conditions.

A

If frequencies were not matched (faster or slower) real load will be seen across the output breaker. If the generator’s frequency was less than the bus frequency, the generator would act as a load (motor) to the bus and a reverse power protective trip may occur.

35
Q

Identify conditions for which a thermal overload protection function is used in motors.

A

The amount of time it takes for the bimetallic element to bend, or the solder to melt in the pot, and trip the motor depends on the amount of overcurrent. A large overload heats the element quickly; a small overload requires more time.

36
Q

Describe the function of a thermal overload protection device.

A

A thermal overload protective device prevents damage to motors due to an overcurrent condition not severe enough to trip the instantaneous, short, or long time overcurrent protective devices.

37
Q

Describe the function of a relay device.

A

It is an electrical switching device with one or more contacts that open or close circuits. The switch electromagnetically operates contacts through a movable arm, called an armature. The armature is attracted when the electromagnet is energized and released when the electromagnet de-energized.

38
Q

Identify conditions for which a relay function is used in circuit breakers.

A

Control, Protection, Lockout, and Overload.

39
Q

What is a 52/TC relay?

A

Energized to activate a trip latch, which releases the breaker operating mechanism (52 device) and allows it to open.

40
Q

What is a 52X relay?

A

Energizes to release the closing latch. (Closing spring then closes breaker).

41
Q

What is a 52Y relay?

A

Energizes when X relay energizes. Stays energized until CLOSE signal is removed (electrical close signal). Provides anti-pumping feature of breaker.

42
Q

What is a 27 relay?

A

Undervoltage Relay. Undervoltage can be caused by an overcurrent condition or by improper voltage regulation
leading to an overcurrent condition.

43
Q

What is a 32 relay?

A

It is a reverse power relay which senses power flow backwards through a breaker. These devices are generally used on a generator output breaker to prevent the generator from motoring and eventual damage.

44
Q

What is a 59 relay?

A

It is an Overvoltage Relay which is used to prevent arcing

and possible insulation breakdown due to increased voltage.

45
Q

What is a 63 relay?

A

It is a Pressure Switche Relay and is normally used in a breaker that uses gas or oil to operate. The pressure
switch actuates to prevent operation if the pressure is too low to provide adequate cycling capability.

46
Q

What is a 46 relay?

A

REVERSE PHASE OR PHASE BALANCE CURRENT RELAY: The device compares the power into a system with the power out of a system (such as a breaker or a transformer, for example). If power is not conserved, indicating a phase fault, the differential relay will trip and cause a breaker trip.

47
Q

What is an 86 relay?

A

Lockout Relay: The relay trips electrically, but is held in the trip position by a mechanical latch. Placing the control switch in the stop position can reset some breakers. Others are held in the trip position by a mechanical latch, and must be mechanically reset by locally turning a knob to reset.

48
Q

What is a 50 relay?

A

Instantaneous Overcurrent Relay: Senses a large overload condition and trips the breaker with minimal time delay. This device is set to operate at a high current value that would be anticipated under short circuit conditions.

49
Q

What is a 51 relay - short?

A

Short-Time Overcurrent (51 Device) Usually a ratchet device that allows some time delay (which is variable) before the trip is activated. This allows motor starting currents to be imposed without tripping the breaker unless the current level has not decayed within a certain
time period after the motor start. This device is set for high current but at a trip value less than that of the instantaneous trip.

50
Q

What is a 51 relay - long?

A

Long-Time Overcurrent (also a 51 Device) Usually an oil dashpot device. It allows a long time delay before the trip occurs and is set at a current level slightly above normal. This device senses an overload condition slightly higher than normal full load.

51
Q

What are “a” alpha contacts?

A

Contacts that are normally open, that is open when the relay is de-energized, are designated as (a) contacts

52
Q

What are “b” bravo contacts?

A

Contacts that are normally closed, that is closed when the relay is de-energized, are designated as (b) contacts

53
Q

Given a typical one-line logic diagram, describe the function of the identified components.

A

Review the materials for examples.