Branch Circuits Flashcards
What is the default termination temperature rating for equipment rated at not more than 100A if not marked?
60 ºC
Rule 4-006 (2)(a)
Which recptacles in a dwelling do not require arc fault protection?
Bathroom, Fridge, Counter, Island, Penisular Counter, Sump Pump*
Rule 26-656 (1)
What is the maximum distance a #12 AWG NMD90 cable can go when fed from a 20A overcurrent? Or where in the CEC do you find the answer?
50m
Table 68
What is the max number of outlets that can be placed on a 2-wire branch circuit?
12
Rule 8-304 (1)
Two seperate built in cooking units installed in a dwelling unit shall be permitted to be considered as one range.
True or False?
True
Rule 8-300 (2)
What is the default termination temperature rating for equipment rated at more than 100A if not marked?
75 ºC
Rule 4-006 (2)(b)
How many 15A Branch Circuits are required for receptacles in a single dwelling with twenty-five 5-15R outlets?
3
8-304 (1,2,3)
A single dwelling’s calculated load is 119A. The single dwelling is heated by a central electric furnace.
Where in the CEC do you look to determine how many panelboard branch circuit positions must be provided?
8-108 (1)(b)
A 36A load which only runs for 45mins every hour shall be considered continuous.
True or False?
False.
45mins + 45mins = 1.5hrs
8-104 (3)(a)