Book 8 "Fire pumps" Flashcards

1
Q

Fire pumps are required in buildings that have

A

Combination or Combined Standpipe Systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The primary water supply is from _____ which feed directly to the building fire pump or from _____ which supplies the fire pump

A

City water mains / Internal tanks (onsite water supply)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

FDC’s to a combination or combined sprinkler standpipe system may be considered a ___

A

second source of water.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

FDC’s are plumbed into the ____ of the fire pump

A

discharge side

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Shut off valves are not permitted between ___ and there ___

A

the FDC’s / connections to the standpipe system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A required check valve in this piping will ____

A

prevent the fire pump pressure from reaching the FDC’s

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

FDC’s are located at the base of the building and may be grouped with ___

A

test outlet valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

In newer buildings the test valves are in a ____

A

different location (sometimes in the pump room)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Purpose of the test valves is to permit a period test of building fire pump which is required to pump _____ of it rated capacity

A

150%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Test valves can be identified by their

A

male threads

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

A centrifugal pump with the shaft normally in a horizontal position.

A

Horizontal Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A centrifugal pump with one or more impellers discharging into one or more bowls with a vertical eductor or column pipe used to connect the bowls to the discharge head. They are particularly suitable for fire pump service when the water source is located below ground and where it would be difficult to install any other type of pump below the minimum water level.

A

Vertical shaft turbine pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

These type of pumps are used to maintain a uniform, relatively high pressure on the fire protection system.

A

Pressure Maintenance Pumps (Jockey or make-up pumps)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A jockey pump should be sized to make up the allowable hourly leakage rate within _____ or ____ whichever is larger.

A

10 minutes or 1 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A centrifugal type pressure maintenance pump is

A

preferable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The jockey pump should be set to operate at a pressure of

A

5 to 10 psi higher than the main pumps start pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Automatic air release valve

A

to automatically release air from the pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Located between the pump and the pump discharge check valve, to operate if the pressure exceeds the pressure for which the system components are rated. Water being discharged from the relief valve has to be readily visible or easily detectable by the pump operator.

A

Circulation Relief Valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

A pressure gauge shall be connected near the ___ and a ____ shall be connected to the suction pipe near the pump

A

discharge casting / a compound pressure and vacuum gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

A compound pressure and vacuum gauge is not required on a

A

Vertical Shaft pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

A water measuring device shall be provided to test the pump.

A

Metering Device

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Prior to 1974, generally there was only _____ and ____

A

one fire pump and it was electrical

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Since 1974 buildings over 275’ are required to have _____ pumps, ______

A

three fire pumps, one electrical and two diesel

24
Q

Electric Motor; power shall be supplied by one or more of the following sources =

A

Utility service, Single power station, Emergency Generator.

25
Q

Emergency power was not required in buildings built between _____

A

1960 and 1974

26
Q

Diesel Engine: Governors: Must be provided with a governor capable of regulating the engine speed within a range of ____ between the shutoff and maximum load condition of the pump.

A

10%

27
Q

Diesel Engine: Overspeed shutdown device: It shall shut down the engine at a speed approximately ____ above rated engine speed and must be ____

A

20% / manually reset after overspeed shutdown

Components: tachometer/ oil pressure gauge/ temperature gauge

28
Q

Diesel Engine: Batteries: Each engine shall be provided with _____ . Each battery unit shall have the capacity to maintain cranking speed throughout a _____

A

two storage battery units / six minute cycle

example: 15 seconds of cranking and 15 seconds of rest in 12 consecutive cycles

29
Q

Diesel Engine: Fuel supply: There must be a separate ____ and separate ____ (day tank) for each engine.

A

fuel line / fuel supply tank

30
Q

Diesel Engine: Fuel supply: There shall be a minimum ___ (new post 1974) and _______ (existing 60-74) supply of fuel

A

8 hour / 4 hour

31
Q

Engine Drive Controllers; Basic function of a fire pump controller is to _____ or allow manual starting in case of a problem with the automatic system.

A

start the engine automatically upon a drop in pressure in the riser

32
Q

Engine Drive Controllers: the controller should be located as ______ and always within sight of the engine.

A

as close as practical to the engine it controls

33
Q

Engine Drive Controllers: The controller will start the engine when there is a drop in the water line pressure. This is done by a

A

Mercoid pressure switch, which is independently adjusted to a high (stop) and low (start) setting.

34
Q

The policy in LA for the STOP pressure is set _____ and start pressure is set _____

A

10 PSI below system pressure / 50 PSI below system pressure

35
Q

The run-out timer is used to keep the pump from

A

constantly starting and stopping

36
Q

The run-out timer is normally set for _____ for electric driven fire pumps and _____ for diesel driven fire pumps

A

seven to ten minutes / 30 minutes

37
Q

Run out timers can be set ___

A

manually

38
Q

Four-Position Selector Switch. Test:

A

This momentarily drops the water pressure, closing the pressure (mercoid) switch, thus starting the engine.

39
Q

Four-Position Selector Switch. Auto:

A

Puts the controller in the standby mode. All the automatic functions are ready for operation.

40
Q

Four-Position Selector Switch. Manual: There are ____ for manually cranking the engine from either set of batteries.

A

two manual start push buttons

41
Q

Four-Position Selector Switch. Manual: In the event of low battery condition, _____ may be depressed simultaneously, increasing the battery potential to the start.

A

Both switch

42
Q

Failure Alarm on the Controller: Overcrank lamp. If the engine fails to start at the _______ (six 15-second crank periods separated by five 15-second rest periods) the overcrank lamp will be lit and the audible alarm will sound.

A

end of the six crank attempts

43
Q

Failure Alarm on the Controller: Overspeed: This is an alarm and will also shut down the engine. Overspeed is the only problem that will ____

A

automatically shut down the engine

44
Q

Failure Alarm on the Controller: Loss of battery charger output. The loss of ___ results in the loss of charger output

A

115 volts

45
Q

Status lights: There are ____ on the controller that indicate battery power is available from ____. The third lamp indicates that the control is in _____ position

A

three green lights / battery one and battery two / AUTO

46
Q

Sequential Starting: The controller for each multiple pump unit shall incorporate a sequential timing device to prevent any combination of engines from ____

A

Starting simultaneously

47
Q

Sequential Starting: If water requirements call for more than one pumping unit to operate, the units shall start at intervals of _____

A

five to ten seconds

48
Q

Sequential Starting: If the pressure in the system stays at the START pressure setting of the mercoid pressure switch for ______ the second pump will start

A

four to six seconds

49
Q

Sequential Starting: if the pressure stays there for ____ the third pump will start. Failure of a leading engine to start will not prevent the subsequent engine from starting.

A

six to eight seconds

50
Q

The National Fire Protection Association requires that when the pump room is not constantly attended, an _____

A

audible or visual alarm, powered by a reliable source, be provided at a point of constant attendance.

51
Q

Acceptance Test: Fire pump controllers shall perform not ____ during the acceptance test and shall be operated for a period of at least ____ during each of the tests.

A

less than 10 automatic and 10 manual operations / five minutes at full speed during each of the tests.

52
Q

Fire pumps are required to pump ___ of rated capacity and at a pressure of not less than ____ of it rated pressure for a minimum of ____

A

150% / 65% / 15 minutes

53
Q

Vane type water flow switches are used on wet sprinkler systems to

A

detect water flow

54
Q

Vane type water flow switch: In high-rise structures they will be found in the ____ where the sprinkler pipe comes off the standpipe.

A

Stairshafts

55
Q

Vane type water flow switch: The minimum flow rate for alarm is ____ (equal to one sprinkler head) and operates in ____

A

4 to 10 gpm / 20 to 60 seconds