Book 8 "Fire pumps" Flashcards
Fire pumps are required in buildings that have
Combination or Combined Standpipe Systems
The primary water supply is from _____ which feed directly to the building fire pump or from _____ which supplies the fire pump
City water mains / Internal tanks (onsite water supply)
FDC’s to a combination or combined sprinkler standpipe system may be considered a ___
second source of water.
FDC’s are plumbed into the ____ of the fire pump
discharge side
Shut off valves are not permitted between ___ and there ___
the FDC’s / connections to the standpipe system
A required check valve in this piping will ____
prevent the fire pump pressure from reaching the FDC’s
FDC’s are located at the base of the building and may be grouped with ___
test outlet valves
In newer buildings the test valves are in a ____
different location (sometimes in the pump room)
Purpose of the test valves is to permit a period test of building fire pump which is required to pump _____ of it rated capacity
150%
Test valves can be identified by their
male threads
A centrifugal pump with the shaft normally in a horizontal position.
Horizontal Pump
A centrifugal pump with one or more impellers discharging into one or more bowls with a vertical eductor or column pipe used to connect the bowls to the discharge head. They are particularly suitable for fire pump service when the water source is located below ground and where it would be difficult to install any other type of pump below the minimum water level.
Vertical shaft turbine pump
These type of pumps are used to maintain a uniform, relatively high pressure on the fire protection system.
Pressure Maintenance Pumps (Jockey or make-up pumps)
A jockey pump should be sized to make up the allowable hourly leakage rate within _____ or ____ whichever is larger.
10 minutes or 1 gpm
A centrifugal type pressure maintenance pump is
preferable
The jockey pump should be set to operate at a pressure of
5 to 10 psi higher than the main pumps start pressure.
Automatic air release valve
to automatically release air from the pump
Located between the pump and the pump discharge check valve, to operate if the pressure exceeds the pressure for which the system components are rated. Water being discharged from the relief valve has to be readily visible or easily detectable by the pump operator.
Circulation Relief Valve
A pressure gauge shall be connected near the ___ and a ____ shall be connected to the suction pipe near the pump
discharge casting / a compound pressure and vacuum gauge
A compound pressure and vacuum gauge is not required on a
Vertical Shaft pump
A water measuring device shall be provided to test the pump.
Metering Device
Prior to 1974, generally there was only _____ and ____
one fire pump and it was electrical