Book 1: 2-08 - Heating Boiler Operating Controls Flashcards

1
Q

The high gas pressure cut-off switch can be tested by:
Select one:

A. Slowly raising the boiler pressure above the operating setpoint

B. Slowly closing the main gas valve

C. Slowly covering the air supply to the fan

D. Closing the main gas valve quickly

E. Quickly closing the main burner shut-off valve

A

E. Quickly closing the main burner shut-off valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If the pressure of the gas supplied to the burner increases beyond the maximum required for safe combustion the _____ switch will de-energize the fuel valve.
Select one:

A. High limit

B. Low gas pressure

C. Low air pressure

D. Low water level

E. High gas pressure

A

E. High gas pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The high limit control can be tested by:
Select one:

A. Slowly covering the air supply to the fan

B. Closing the main gas valve quickly

C. Quickly closing the main burner shut-off valve

D. Slowly closing the main gas valve

E. Slowly raising the boiler pressure above the operating setpoint

A

E. Slowly raising the boiler pressure above the operating setpoint

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Controls found on heating boilers include:
1. Operating controls
2. Pressure relief controls
3. High limit cut-off switches
4. Condensate level controls
5. Low limit cut-off switches
Select one:

A. 3, 4, 5

B. 2, 3, 4

C. 3, 4, 5

D. 1, 3, 5

E. 1, 2, 3

A

D. 1, 3, 5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The On-Off pressure controller contains two adjustable variables, one is the pressure adjustment and the other is the:
Select one:

A. Operating lever

B. Cut-in Lever

C. Leveling indicator

D. Pressure bellows

E. Differential adjustment

A

E. Differential adjustment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The Modulating fire control system uses _____ to control the combustion process.
Select one:

A. Air on-off control

B. Fixed fuel flow and variable air flow

C. Fuel on-off control

D. Fixed air flow and variable fuel flow

E. Variable fuel/air flow

A

E. Variable fuel/air flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The low air pressure cut-off switch can be tested by:
Select one:

A. Slowly raising the boiler pressure above the operating setpoint

B. Slowly covering the air supply to the fan

C. Slowly closing the main gas valve

D. Quickly closing the main burner shut-off valve

E. Closing the main gas valve quickly

A

B. Slowly covering the air supply to the fan

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An automatic/manual selector switch is provided on a boiler with the following burner control system.
Select one:

A. High-Low fire control

B. Modulating fire control

C. On-Off fire control

D. Operating limit fire control

E. High limit fire control

A

B. Modulating fire control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The high limit control of a steam heating boiler should operate at the:
Select one:

A. Blowdown pressure of the safety valve

B. Set pressure of the safety valve

C. Maximum allowable working pressure

D. Between the set pressures of the operating control and safety valve

E. Cut-out pressure of the operating control

A

D. Between the set pressures of the operating control and safety valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The On-Off method of steam heating boiler burner control uses the _____ as the sensed variable.
Select one:

A. Feedwater pressure

B. Drum water level

C. Boiler steam temperature

D. Boiler steam flow

E. Boiler steam pressure

A

E. Boiler steam pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Damper position switches are found on boilers with the following burner control systems:
1. On-Off control
2. High- Low control
3. Modulating control
4. High Limit control

Select one:

A. 2,3
B. 1,2
C. 1,3
D. 3,4
E. 4,5

A

A. 2,3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The high gas pressure cut-off switch can be tested by:

Select one:

A. Slowly closing the main gas valve
B. Slowly raising the boiler pressure above the operating setpoint
C. Closing the main gas valve quickly
D. Slowly covering the air supply to the fan
E. Quickly closing the main burner shut-off valve

A

E. Quickly closing the main burner shut-off valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The High-Low fire control method requires two pressure controllers, one is called the high-low fire control and the other is called the:

Select one:

A. Modulating fire control
B. High limit fire control
C. Operating limit pressure control
D. On-Off fire control
E. Operating limit fire control

A

C. Operating limit fire pressure control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

If the pressure of the gas supplies tk the burner drops below a minimum value the _______ switch will de-energize the fuel valve.

Select one:

A. Low water level
B. Low air pressure
C. High gas pressure
D. High limit.
E. Low gas pressure

A

E. Low gas pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The hot water heating boiler burner control uses the ______ as the sensed variable.

Select one:

A. Feed water pressure
B. Boiler steam temperature
C. Boiler water temperature
D. Drum water level
E. Boiler water pressure

A

C. Boiler water temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The low air pressure cut-off switch can be tested by:

Select one:

A. Slowly covering the air supply
B. Slowly raising the boiler pressure above the operating set point
C. Slowly closing the main gas valve
D. Closing the main gas valve quickly
E. Quickly closing the main burner shut-off valve

A

A. Slowly covering the air supply to the fan

17
Q

An automatic/manual selector switch is provided on a boiler with the following burner control system.

Select one:

A. High-low fire control
B. On-Off fire control
C. Operating limit fire control
D. High limit fire control
E. Modulating fire control

A

E. Modulating fire control

18
Q

The high limit control of a steam heating boiler should operate at the:

Select one:

A. Set pressure of the safety valve
B. Cut-out pressure of the operating control
C. Maximum allowable working pressure
D. Between the set pressures of the operating control and safety valve
E. Blowdown pressure of the safety valve

A

D. Between the set pressures of the operating control and safety valve

19
Q

If the pressure of the gas supplied to the burner increases beyond the maximum required for safe combustion the _____ switch will de-energize the fuel valve.

Select one:

A. Low air pressure
B. Low water level
C. High gas pressure
D. Low gas pressure
E. High limit

A

C. High gas pressure

20
Q

The On-Off pressure controller contains two adjustable variables, one is the pressure adjustment and the other is the:

Select one:

A. Differential adjustment
B. Pressure bellows
C. Cut-in Lever
D. Levelling indicator
E. Operating lever

A

A. Differential adjustment

21
Q

The low gas pressure cut-off switch can be tested by:

Select one:
A. Slowly closing the main gas valve
B. Slowly raising the boiler pressure above the operating setpoint
C. Slowly covering the air supply to the fan
D. Quickly closing the main burner shut-off valve
E. Closing the main gas valve quickly

A

A. Slowly closing the main gas valve

22
Q

Controls found on heating boilers include:
1. Operating controls
2. Pressure relief controls
3. High limit cut-off switches
4. Condensate level controls
5. Low limit cut-off switches

Select one:
A. 2,3,4
B. 3,4,5
C. 1,2,3
D. 3,4,5
E. 1,3,5

A

E. 1,3,5

23
Q

The high limit control can be tested by:
Select one:

A. Closing the main gas valve quickly
B. Slowly raising the boiler pressure above the operating setpoint
C. Quickly closing the main burner shut-off valve
D. Slowly covering the air supply to the fan
E. Slowly closing the main gas valve

A

D. Slowly raising the boiler pressure above the operating setpoint

24
Q

The modulating fire control system uses_____ to control the combustion process.
Select one:

A. Air on-off control
B. Fixed fuel flow and variable air flow
C. Fuel on-off control
D. Variable fuel/air flow
E. Fixed air flow and variable fuel flow

A

D. Variable fuel/air flow

25
Q

Three of the four distinct methods of burner operation control for a steam boiler are:
1. On-off control
2. Damping control
3. Modulating control
4. High limit control
5. Multiple burner control

Select one:
A. 3,4,5
B. 2,3,4
C. 1,2,3
D. 2,3,5
E. 1,3,4

A

E.1,3,4

26
Q

The on-off method of steam heating boiler burner control uses the _____ as the sensed variable.
Select one:

A. Boiler steam temperature
B. Drum water level
C. Feedwater pressure
D. Boiler steam pressure
E. Boiler steam flow

A

D. Boiler steam pressure

27
Q

During boiler operation if the combustion air pressure drops to low the ______ switch will de-energize the fuel valve.
Select one:

A. Low air pressure
B. Low water level
C. High limit
D. High gas pressure
E. Low gas pressure

A

A. Low air pressure

28
Q

If the pressure of the gas supplies to the burner drops below a minimum value the _____ switch will de-energize the fuel valve.
Select one:

A. Low gas pressure
B. High gas pressure
C. Low air pressure
D. High limit
E. Low water level

A

A. Low gas pressure

29
Q

If the pressure of the gas supplied to the burner increased beyond the maximum required for safe combustion the ____ switch will de-energize the fuel valve.
Select one:

A. Low gas pressure
B. High gas pressure
C. Low water level
D. Low air pressure
E. High limit

A

B. High gas pressure

30
Q

The low air pressure cut-off switch can be tested by:
Select one:

A. Slowly raising the boiler pressure above the operating setpoint
B. Quickly closing the main burner shut-off valve
C. Closing the main gas valve
D. Slowly closing the main gas valve
E. Slowly covering the air supply to the fan

A

E. Slowly covering the air supply to the fan