Book 1: 2-08 - Heating Boiler Operating Controls Flashcards
The high gas pressure cut-off switch can be tested by:
Select one:
A. Slowly raising the boiler pressure above the operating setpoint
B. Slowly closing the main gas valve
C. Slowly covering the air supply to the fan
D. Closing the main gas valve quickly
E. Quickly closing the main burner shut-off valve
E. Quickly closing the main burner shut-off valve
If the pressure of the gas supplied to the burner increases beyond the maximum required for safe combustion the _____ switch will de-energize the fuel valve.
Select one:
A. High limit
B. Low gas pressure
C. Low air pressure
D. Low water level
E. High gas pressure
E. High gas pressure
The high limit control can be tested by:
Select one:
A. Slowly covering the air supply to the fan
B. Closing the main gas valve quickly
C. Quickly closing the main burner shut-off valve
D. Slowly closing the main gas valve
E. Slowly raising the boiler pressure above the operating setpoint
E. Slowly raising the boiler pressure above the operating setpoint
Controls found on heating boilers include:
1. Operating controls
2. Pressure relief controls
3. High limit cut-off switches
4. Condensate level controls
5. Low limit cut-off switches
Select one:
A. 3, 4, 5
B. 2, 3, 4
C. 3, 4, 5
D. 1, 3, 5
E. 1, 2, 3
D. 1, 3, 5
The On-Off pressure controller contains two adjustable variables, one is the pressure adjustment and the other is the:
Select one:
A. Operating lever
B. Cut-in Lever
C. Leveling indicator
D. Pressure bellows
E. Differential adjustment
E. Differential adjustment
The Modulating fire control system uses _____ to control the combustion process.
Select one:
A. Air on-off control
B. Fixed fuel flow and variable air flow
C. Fuel on-off control
D. Fixed air flow and variable fuel flow
E. Variable fuel/air flow
E. Variable fuel/air flow
The low air pressure cut-off switch can be tested by:
Select one:
A. Slowly raising the boiler pressure above the operating setpoint
B. Slowly covering the air supply to the fan
C. Slowly closing the main gas valve
D. Quickly closing the main burner shut-off valve
E. Closing the main gas valve quickly
B. Slowly covering the air supply to the fan
An automatic/manual selector switch is provided on a boiler with the following burner control system.
Select one:
A. High-Low fire control
B. Modulating fire control
C. On-Off fire control
D. Operating limit fire control
E. High limit fire control
B. Modulating fire control
The high limit control of a steam heating boiler should operate at the:
Select one:
A. Blowdown pressure of the safety valve
B. Set pressure of the safety valve
C. Maximum allowable working pressure
D. Between the set pressures of the operating control and safety valve
E. Cut-out pressure of the operating control
D. Between the set pressures of the operating control and safety valve
The On-Off method of steam heating boiler burner control uses the _____ as the sensed variable.
Select one:
A. Feedwater pressure
B. Drum water level
C. Boiler steam temperature
D. Boiler steam flow
E. Boiler steam pressure
E. Boiler steam pressure
Damper position switches are found on boilers with the following burner control systems:
1. On-Off control
2. High- Low control
3. Modulating control
4. High Limit control
Select one:
A. 2,3
B. 1,2
C. 1,3
D. 3,4
E. 4,5
A. 2,3
The high gas pressure cut-off switch can be tested by:
Select one:
A. Slowly closing the main gas valve
B. Slowly raising the boiler pressure above the operating setpoint
C. Closing the main gas valve quickly
D. Slowly covering the air supply to the fan
E. Quickly closing the main burner shut-off valve
E. Quickly closing the main burner shut-off valve
The High-Low fire control method requires two pressure controllers, one is called the high-low fire control and the other is called the:
Select one:
A. Modulating fire control
B. High limit fire control
C. Operating limit pressure control
D. On-Off fire control
E. Operating limit fire control
C. Operating limit fire pressure control
If the pressure of the gas supplies tk the burner drops below a minimum value the _______ switch will de-energize the fuel valve.
Select one:
A. Low water level
B. Low air pressure
C. High gas pressure
D. High limit.
E. Low gas pressure
E. Low gas pressure
The hot water heating boiler burner control uses the ______ as the sensed variable.
Select one:
A. Feed water pressure
B. Boiler steam temperature
C. Boiler water temperature
D. Drum water level
E. Boiler water pressure
C. Boiler water temperature