What does VOID R stand for ?
V- violation of law O- operating efficiency decreased to dangerous level I- injury to personnel D- damage to equipment or apparatus R- response time :60 secs
What are the Basic Fire Prevention Principals ?
Limitation
Isolation
Separation
Elimination
What is the purpose of the station fire prevention program ?
Obtain complete coverage of the city
What % of fire prevention should be completed every month ?
10%
Small arms ammo is defined as
.75 caliber or less
How many lbs of small arms ammo requires approval of Fire Prevention Bureau as to location , fire protection , warning and placards ?
> 1,000 lbs
Small arms in excess of ___ lbs shall be stored in a room of 1- hour fire resistive construction
5,000 lbs
Drums containing corrosive materials shall not be stacked more than ___containers high or > _____ ft high
2 containers high
10 feet tall
The storage of CORROSIVE materials outside of buildings shall be at least ____ ft away from building .
5 feet
Flammable aerosols may be displayed in retail sales areas ONLY if they are limited to _____gallons
30
Flammable aerosols > _____ gallons shall be stored in a room separate from retail sales
60 gallons
All EXISTING building that are ____ stories or more which contain group R-1 occupancies shall have sprinkler systems .
3 or more stories
When any fire protection construction doesn’t meet the min requirements , and needs to be restored or conformed, who do you notify?
Building and safety with an F-338
Sprinklers in compliance with DOROTHY MAE may use plastic pipe for what?
Laterals
Are the storage of flammable liquids allowed in basements ?
NO! Strictly prohibited
When is a sleeping room allowed in a basement ?
Every room must have :
1 operable window or
Exterior door for escape
Dispenser hoses for motor fuel in auto fueling stations are not to exceed
14 feet
Repair work involving open flame shall be kept at least _____feet from storage or garages
25 feet
Heaters in auto fueling stations must be at least _____ft from the nozzle
10 feet
All haz vegetation or native brush within ____ ft of any structure or ____ft from the road must be no > ____in tall
10 feet
200 feet
3 in
What is the purpose of cutting the brush down to 3”?
Leave the root undisturbed
All trees, shrubs and bushes shall be removed within ____ ft of CHIMNEYS
10 feet
Who does the company commander contact to get a no smoking replacement sign ?
DOT
All curtains in assemblage areas must be fire retardant and considered good for how many years ?
5 years
How many gallons is a dip tank required to have a permit ?
150 gallons or more
A lightbulb should have a clearance of how many inches from combustible materials ?
18 inches
Every fuel dispenser must have a fire extinguisher with a ____rating within ____ft of each one .
2A 20BC
75 feet
What form is attached when a piece of equipment or device is condemned ?
An F-336
What is a F-211?
Citation
Any complaint of a hazard received at the fire station should be inspected no later than….
No later than the next day