Basic Installation Procedures Flashcards
A PLC is best mounted in a motor control centre. True or False?
False
Communication cables must be kept a minimum of ____mm from power cables and cross the power cables at ________
300mm, right angles
Grounding and shielding is done in a _______ fashion to prevent ________ loops
radial, ground
Does the CEC allow the load side of a DC power supply (system) to be left ungrounded? What is usually done? Why?
Yes. CEC Rule 10-102(1) allows this if it is not more than 50V. It is usually grounded anyway, to prevent the above-ground potential from becoming excessive through static charging, misconnection or wiring fault.
What are five possible CPU power supply sources in order from least to most preferable
- Raw line power
- Isolation transformer
- Regulating transformer
- Power conditioner
- UPS
What are four reasons to include a master control relay in a PLC program?
Override for:
- PLC hardware failure
- Programming blunders
- Some wiring mistakes
- Provide low-voltage protection