BAL-006 Inadvertent Interchange provides a process for Balancing Authorities to _________.
ensure that over the long term, they do not excessively depend on other Balancing Authority Area in the Interconnection to meet their demand or interchange obligation.
Factors that cause inadvertent interchange include…
- Frequency Support
- Load changed within the Balancing Authority
- Generator Lag
- Metering Errors
- Unilateral Inadvertent Interchange Payback
- Human Error
Two types of Inadvertent Interchange are:
- Primary or Unintentional Inadvertent Interchange
- Secondary or Non-scheduled Inadvertent Interchange
Primary or Unintentional Inadvertent Interchange can be caused by_______.
- human error
- scheduling error
- metering error
Secondary or Non-scheduled Inadvertent Interchange can be caused by _________.
- Frequency Support
- Regulation
- Governor Response
What are the two type of payback for inadvertent interchange
- Bilateral Payback
- Unilateral Payback
Bilateral Payback is accomplished via
interchange schedule with another Balancing Authority with inadvertent interchange accumulations in opposite direction. i.e. Sink Balancing Authority is positive while Source Balancing Authority is negative
Unilateral Payback is accomplished via
controlling to a target of non-zero ACE so long as not burden to the interconnection.