Aux Feed Water Flashcards
1
Q
How do you ensure Water to the steam generators on a Loss of AC
A
- CST + TDAFP
- EDG + MDAFP + CST
2
Q
How do you ensure Water to the steam generators on a loss of main feed water
A
- CST
- MDAFP
- TDAFP
3
Q
How do you ensure Water to the steam generators on a Loss of condensate storage tank level
A
CRV- 51 CST crosstie
4
Q
How do you ensure Water to the steam generators on a steam line rupture
A
Steam Generator Stop Valves close
5
Q
How do you ensure Water to the steam generators on a Feed Water Line Rupture
A
FWI signal, FMO’s and FRV’s Close. Feed with aux feed
6
Q
MDAFP autostarts
A
- Both Main Feed Pumps Trip (if switch is in auto)
- Amsac
- Loadshed
- Lo Lo Steam Generator Level
- SI
7
Q
MDAFP trips
A
- Load Shed
- Overload
- Over Current
8
Q
TDAFP Autostarts
A
- Undervolt 4kv rcp bus
- SI
- Amsac
9
Q
TDAFP Trips
A
- Electric overspeed 108%
- Mechanical Overspeed 111%
- Manual
10
Q
Operator actions involving aux feed
A
- Crosstie aux feed between units
- valve in bearing cooling
- reset trip and throttle valve
- mechanical overspeed (harpooning the shaft) must be reset locally
11
Q
How do you establish local control of aux feed to maintain steam generator level control
A
- East main steam stop enclosure or startup blowdown flashtank room
- take local control with lsi’s
- with aux feed pumps running throttle manual valves to control aux feed flow to steam generator