Auc5 & Add General Flashcards

1
Q

Artist Loft: It should be noted that the Multiple Dwelling Law does not permit the conversion of a loft building to a Multiple Dwelling. Therefore, the occupancy shall not exceed ____ separate individual units used for living purposes

A

two

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Artist Loft: The building must not have any type of occupancy listed as a ______________

A

high fire hazard

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The artist must notify the____________in writing of the exact location of the studio in question so that an inspection can be made to check for compliance with these requirements

A

Department of Buildings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Artist Loft DOB sign Spec.

Size/material?

A

metal 8”x10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Artist Loft DOB sign Spec

____Inch (color) Letters on a (color) background

A

2” black letters white background

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Artist Loft DOB sign Spec

How far above sidewalk level?

A

seven feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Artist Loft DOB sign Spec

Where does it go? And what does it say?

A

As close as possible to the main entrance on front wall outside of building reading
A.I.R.
3F (3rd floor)
R (rear)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

CDA insp
When during the course of the construction of a new building the working deck reaches a height of __ feet or greater above the ground in a building for which a standpipe system will be required, a permanent or temporary standpipe system shall be kept in a state of readiness at all times for use by fire-fighting personnel. The standpipe system shall serve all floors where the permanent stairs are required.

A

75

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

CDA: No standpipe shall be considered to be in a state of readiness unless it is painted___

A

red

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

CDA: Can a system be maintained dry?

A

-When freezing conditions may be encountered, the system in whole, or the part of the system subject to freezing conditions, shall be maintained as a dry system.
(same for below ground)
-Existing standpipe systems in structures undergoing a full demolition shall be maintained as dry standpipes.
-

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

CDA
At the commencement of demolition, the standpipe risers and sprinklers shall be capped above the outlet on the floor ________

A

immediately below the floor being demolished

so as to maintain the standpipe system/sprinkler on all lower floors for Fire Department use. Cutting and capping of standpipes/sprinklers during demolition work shall be performed only by a licensed master plumber or licensed master fire suppression piping contractor who has obtained a permit for such work. Standpipe hose, nozzles and spanners are not required to be maintained and may be removed at any time. The red paint shall be maintained during any demolition operations. All existing house check valves shall remain in place until completion of the demolition work

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When, during the course of the construction of a new building which will have a occupiable space at a depth of ___ feet or greater below the level of the ground in a building for which a standpipe system will be required, a permanent or temporary standpipe system shall be installed and shall be kept in a state of readiness at all times for use by fire-fighting personnel. The standpipe system shall serve all stories below grade and shall be installed as soon as a temporary or permanent stair is installed below grade

A

75

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
CDA
STANDPIPE PRESSURIZED ALARM SYSTEMS
required in two situations
1.\_\_\_\_\_
2.\_\_\_\_
A

Vacant Buildings Being Demolished: Existing standpipes must be dry standpipes and have an air-pressurized alarm.
• New Buildings Higher than 75 Feet: Temporary and permanent dry standpipes must have an air-pressurized alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q
CDA 
air pressurized standpipe
2 situations contractors must notify FD
1\_\_\_\_\_\_\_\_\_\_\_\_
2\_\_\_\_\_\_\_\_\_\_\_
A

Prior Notification for Scheduled Work: Contractors must notify the Fire Department before any planned alarm deactivation.
• Out of Service Standpipes: Contractors must notify the Fire Department

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

CDA
Fire department hose connections shall be kept free from obstruction and shall be marked by a ___________
Does this apply to sprinklers as well?

A

metal sign reading, “Standpipe Connection” and by a red light at night.
Yes sprinklers too

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

CDA

Can standpipes be used for other purposes?(supplying air or water for construction)

A

Standpipes may be used for a purpose other than to supply water for firefighting operations, including but not limited to supplying water or compressed air for construction or demolition operations, provided at least one standpipe riser is maintained at all times for firefighting operations. Where the standpipe is used to supply water for construction or demolition operations and freezing conditions may occur, the standpipe shall be completely drained after use to prevent freezing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

CDA
All exposed standpipes and sprinkler piping must be painted red.
Are there any exceptions?

A

The law outlines specific exceptions, such as branch piping.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

CDA
How are valve handles color coded?
What size buildings must comply with new requirements?

A

red yellow green…SP, sprinkler, combo

ALL size must comply

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

CDA

Can sprinklers be deactivated during an alteration?

A

NO
Sprinklers during alteration. Existing sprinkler systems in buildings undergoing an alteration shall be maintained: Required means of egress, existing structural elements, fire protection devices, and sanitary safeguards shall be maintained at all times during construction or demolition operations in existing buildings. Required means of egress shall not be obstructed in any manner that would destroy the full effectiveness of such means of egress.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

CDA Egress Requirements:
During the course of construction of a new building, or in spaces being added to an existing building, at least one permanent stair shall be brought to within a distance of ___ feet or __ floors below the working deck at all times. In all other locations where permanent stairs will be required, a temporary or permanent stair shall be brought to within a distance of __ feet or __ floors below the working deck at all times.
(Same for both)

A

40 feet 4 floors
• Stairs in an existing building undergoing alteration or a partial demolition shall be maintained.
• All stairs in a building undergoing construction or demolition shall be lighted at all times and kept free of equipment, debris, and material.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

CDA Elevator in readiness:
Whenever construction or demolition work reaches a height greater than __ feet, at least one elevator meeting the requirements of Chapter 30, or a hoist meeting the requirements of Section 3318 shall be kept in readiness at all times for Fire Department use. The maximum distance between the highest accessible floor from a temporary elevator or hoist and the working deck of the building under construction or demolition shall be no more than __ feet or __ floors

A

75

75…..7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

CDA Elevator in readiness:
In concrete construction, the working deck is ____
In steel construction the working deck is______

A

In concrete construction, the working deck is the floor being formed.
In steel construction the working deck is the floor where the metal decking and steel components are being placed before concrete is poured.
If the travel of the hoist cannot be increased due to inclement weather, it shall be increased by the end of the next working day

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

GENERAL PRECAUTIONS AGAINST FIRE

Kindling, building, maintaining or using an open fire is prohibited. What are the 5 exceptions?

A
  • Portable outdoor barbecues as authorized by FC 307.5 see section 5 below.
  • Outdoor noncommercial barbecue fires in equipment provided by and located in city parks where such open fires are allowed by the Department of Parks and Recreation.
  • In connection with training of fire brigades or similar purposes by persons or entities where such training is required by law, rule or regulation.
  • Approved open fires used for special effects in connection with television, motion picture, theatrical and other entertainment productions.
  • Coke-fueled salamanders at a construction site in accordance with FC307.6 and the rules.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

GENERAL PRECAUTIONS AGAINST FIRE
Open fires allowed pursuant to FC 307.1 may only be kindled, built, maintained or used with the prior written authorization of the agencies with regulatory jurisdiction, property owner and other required approvals, and only when such open fires are maintained in compliance with all conditions of such authorization or approval. Who may prohibit the kindling, building, maintaining or use of open fire or order the extinguishment of any open fire allowed by this section, upon a determination that such open fire will create an undue hazard because of conditions in the surrounding environment?

A

The commissioner

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

GENERAL PRECAUTIONS AGAINST FIRE
Must open fires be constantly attended?
If an extinguisher is on hand what is the minimum rating?

A

YES, Open fires shall be constantly attended until the fire is extinguished. A minimum of one portable fire extinguisher complying with the requirements of FC 906.1 with a minimum 4-A rating or other approved on-site fire-extinguishing equipment, garden hose connected to an approved water supply, shall be available for immediate use

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

GENERAL PRECAUTIONS AGAINST FIRE
Open Fires in regard to fire pits and chimineas
1.Do all of these devices meet the definition of open fire?
2.What enforcement action is required if it is not a chronic problem?
3.If a chronic problem?

A
  1. Sometimes these devices do not meet the literal definition of “Open Fires”. Regardless of the definition
  2. if these devices are found by Fire officials they should order the use of these devices discontinued immediately. No further enforcement action is required other than the discontinuance of use at this time
  3. If the use of an outdoor fireplace becomes a chronic problem at the same location the Fire official should order the use of the outdoor fireplace discontinued immediately and serve a summons at this time for failure to comply with FC 307.1 and/or FC 307.2.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

GENERAL PRECAUTIONS AGAINST FIRE

What is the exception to the fire pit chiminea rule?

A

Outdoor decorative gas appliance; Fire pit - outdoor; Gas appliance – outdoor, as per DOB BUILDINGS BULLETIN 2015-016 dated June 2, 2015. (This applies to natural gas fueled stationary appliances/fire pits, no other fuel sources are allowed.)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

GENERAL PRECAUTIONS AGAINST FIRE
Outdoor decorative gas appliances are stationary or built-in appliances connected to a fixed fuel piping system for use in outdoor spaces only and do not incorporate a venting system. The primary function of this appliance lies in the aesthetic effect of the flame. Acceptable outdoor decorative gas appliances shall be listed and labeled by an approved agency.
What are the 4 design requirements?

A
  1. An emergency shut off gas valve shall be installed.
  2. Outdoor decorative gas appliances shall be located outdoors and at least 5 feet from any building or structure.
  3. Outdoor decorative gas appliances shall not be located beneath, or closer than 5 feet to combustible decorations and combustible overhangs, awnings, sun control devices or similar combustible attachments to buildings or structures.
  4. Outdoor decorative gas appliances shall not be located within 5 feet of exits or exit discharges
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

GENERAL PRECAUTIONS AGAINST FIRE Outdoor decorative gas appliances are stationary or built-in appliances connected to a fixed fuel piping system for use in outdoor spaces only and do not incorporate a venting system. The primary function of this appliance lies in the aesthetic effect of the flame. Acceptable outdoor decorative gas appliances shall be listed and labeled by an approved agency.
What are the 3 installation requirements?

A
  1. A valid FDNY permit shall be obtained for the use of outdoor decorative gas appliances with an open flame in accordance with NYC FC Section 105.6
  2. Fire extinguishers shall be installed at a minimum of 10 feet and a maximum of 20 feet from the outdoor decorative gas appliance.
  3. Furniture within 5 feet from the fire-pit shall have a flame-retardant coating. Additional fire loads shall not be permitted.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

GENERAL PRECAUTIONS AGAINST FIRE
Portable outdoor barbecues burning charcoal, powered by electricity, or fueled by LPG containers or piped natural gas may be stored and used on any residential premises in compliance with the requirements of this section and the rules.
The total grate area of a portable outdoor barbecue shall not exceed __ square feet

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

GENERAL PRECAUTIONS AGAINST FIRE
Portable outdoor barbecues shall not be stored or used within __ feet of any combustible waste, combustible material, or any combustible building surface, including combustible roofs and decks. To the maximum extent feasible, windows, doors and other building openings within __ feet of a barbecue in use shall be kept closed. An entrance door shall be closed immediately after entering or exiting the building while the barbecue is in use.(same number)

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

GENERAL PRECAUTIONS AGAINST FIRE
A garden-type hose attached to a water supply, or a minimum of one portable fire extinguisher complying with the requirements of FC906 with a minimum__ rating, shall be provided for any portable outdoor barbecue, and shall be readily accessible whenever the portable outdoor barbecue is in use. A portable fire extinguisher complying with the requirements of FC906 and with a Class __ rating shall be provided for any portable outdoor barbecue used for commercial cooking purposes, and shall be readily accessible whenever such barbecue is in use. (FC 307.5.4)

A

4-A rating

K rating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

GENERAL PRECAUTIONS AGAINST FIRE
Group R-2 occupancies (R-2 = Apartment houses, etc.)
Only portable outdoor barbecues designed for use with LPG containers with a capacity of 16.4 ounces may be stored or used on the premises of a Group R-2 occupancy. Indoor storage of 16.4-ounce LPG containers for this or any other purpose is limited to a maximum of ____ such containers per dwelling unit.

A

four

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

GENERAL PRECAUTIONS AGAINST FIRE
Group R-3 occupancies (R3 = 1 or 2 family dwellings)
Portable outdoor barbecues designed for use with LPG containers with a capacity of 20 pounds or LPG containers with a capacity of 16.4 ounces may be stored or used on the premises of a Group R-3 occupancy. Twenty-pound LPG containers shall not be stored or used indoors, or on any rooftop or balcony. A maximum of __ 20-pound LPG containers may be used to fuel a portable outdoor barbecue. Indoor storage of 16.4-ounce LPG containers for this or any other purpose is limited to a maximum of___such containers per dwelling unit. (FC 307.5.6.2)

A

two

four

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

GENERAL PRECAUTIONS AGAINST FIRE
Storage in buildings
Storage of combustible materials in buildings shall be maintained in a neat, orderly manner. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. (FC 315.2)
Ceiling clearance
Storage shall be maintained __ feet or more below the ceiling in areas of buildings not protected by a sprinkler system, or a minimum of 18 inches below sprinkler head deflectors in areas protected by a sprinkler system. (FC 315.2.1)

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

GENERAL PRECAUTIONS AGAINST FIRE
Exterior access to shaftways & Interior access to shaftways
Door or window openings to a hoistway or shaftway from the interior of the building OR
Outside openings accessible to the department and which open directly on a hoistway or shaftway communicating between two or more floors in a building shall be plainly marked with the word “_____” in (color) letters at least __ inches high on a (color) background. Such warning signs shall be placed so as to be readily discernible from the outside of the building.

A

SHAFTWAY
red
6
white

Exception: Marking shall not be required on shaftway openings which are readily discernible as openings onto a shaftway by the construction or arrangement.

37
Q

GENERAL PRECAUTIONS AGAINST FIRE
Rooftop conduits and piping
To the maximum extent practicable, conduits, including cable trays, and piping, shall be installed at rooftop locations where they do not obstruct rooftop access landings, clear path or required clearances. If it is impracticable to avoid these areas, conduits and piping shall be designed and installed to facilitate access and minimize tripping hazards. Steps or ramps shall be provided that are constructed of noncombustible material, equipped with railings, and designed to allow any conduit or piping installations that exceed ___foot/feet in height above the roof surface, or more than ___inches in width, to be readily traversed. Steps, ramps, platforms and ladders shall not be placed in areas or in a manner that would obstruct any door or means of egress.

A

1 foot

24 inches

38
Q
GENERAL PRECAUTIONS AGAINST FIRE
All conduits and piping installations shall be color-coded with continuous, durable and weatherproof reflective or luminescent markings as follows, and for conduit and piping installed after July 1, 2014, shall be continuously labeled in an approved manner to indicate its contents:(colors hint: one is two colors. one must be labeled in addition to the color)
1. High voltage wiring?
2. Low voltage wiring?
3. Natural gas piping?
4. Other compressed gas piping?
5. Fuel oil piping?
A

1 red
2 orange
3 yellow
4 Yellow, labeled at regular intervals with the type of gas.
5 Yellow with black stripes. (FC 504.4.7)

39
Q

GENERAL PRECAUTIONS AGAINST FIRE
Multi-floor dwelling units (Duplex/ Triplex)
The entrance door to a multi-floor dwelling unit in a Group R-1 or Group R-2 building or occupancy shall be identified on the door jamb on the public corridor side of the door by an approved fire emergency marking, not more than __inches from the bottom of the door, indicating the dwelling unit number and/or letter.
What other marking is required for the duplex/triplex apts?

A

12 inches

In addition, every door of each such multi-floor dwelling unit that opens to a public corridor or other means of egress shall be identified on the public corridor side of the door by one or more upward or downward-pointing arrows indicating the direction(s) of the other floor(s) to which the multi-floor dwelling unit is connected.

40
Q

GENERAL PRECAUTIONS AGAINST FIRE
Apartment and sleeping rooms
Except as otherwise provided in FC505.4.1, and except in buildings protected throughout by a sprinkler system, in a Group R-1 or R-2 building or occupancy with more than ___ dwelling units on a floor, each dwelling unit shall be identified on the door jamb on the public corridor side of the door by an approved fire emergency marking, not more than __ inches from the bottom of the door, indicating the dwelling unit number and/or letter.

A

eight

12

41
Q

GENERAL PRECAUTIONS AGAINST FIRE
Stairwell signage
Except in buildings protected throughout by a sprinkler system, each stairwell door in a building or occupancy subject to compliance with the requirements of FC505.4.1 or FC505.4.2 shall be identified as a stairwell door on the door jamb on the public corridor side of the door with an approved marking or sign not more than ___ inches from the bottom of the door, unless such stairwell entrance has been marked in compliance with Section 1026.11 of the Building Code.
(FC 505.4.3)

A

12

42
Q

GENERAL PRECAUTIONS AGAINST FIRE
STORAGE FOR ALL OCCUPANCIES ESTABLISHED OR ALTERED ON OR AFTER JULY 1, 2008 (2008 Fire Code)
Storage of flammable and combustible liquids below grade
One is not allowed, one requires a sprinkler
Flamable Liquids
Combustable Liquids

A

• Flammable liquids in any amount shall not be allowed in basements, cellars, or other areas below grade.
• Combustible liquids shall be allowed to be stored in basements, cellars, or other area below grade provided that these areas are protected throughout by a sprinkler system.
(FC 3404.3.5.1

43
Q

GENERAL PRECAUTIONS AGAINST FIRE
STORAGE FOR ALL OCCUPANCIES ESTABLISHED OR ALTERED ON OR AFTER JULY 1, 2008 (2008 Fire Code)
What is the exception to combustible liquids below grade for the sprinkler requirement? Fire resistance rating time?

A

Exception: Class IIIB combustible liquids may be stored in basements, cellars and other areas below grade that are not protected throughout by a sprinkler system when stored in a room or other area that is segregated, vertically and horizontally, from surrounding spaces by a fire separation of not less than 2-hour fire-resistance rating and such room or other area is protected throughout by a sprinkler system.

44
Q

GENERAL PRECAUTIONS AGAINST FIRE
(NOT mercantile)Are the provisions of storing flammable and combustible liquids below grade applicable to lawfully existing facilities established prior to July 1, 2008?
After an alteration?

A

NO….after alteration…YES
A. The provisions of FC 3404.3.5.1 are not applicable to lawfully existing facilities established prior to July 1, 2008. Such facilities that cannot comply with the requirements of the new code may continue to store flammable and combustible liquids below grade in accordance with the laws and regulations in effect at the time the facility was lawfully established. However, if the facility as it relates to such below grade storage undergoes alteration; such alteration would be required to comply with such new provisions.
B. any amount of below grade storage of flammable or combustible liquid would trigger the sprinkler system requirement

45
Q

GENERAL PRECAUTIONS AGAINST FIRE
REQUIREMENTS ONLY FOR MERCANTILE OCCUPANCIES PRE EXISTING JULY 1, 2008
Are sprinklers required for flammable and combustible liquids?

A

All mercantile occupancies, lawfully pre-existing on July 1, 2008 were required to comply with the requirements of Local Law 26 of 2002. This local law required the installation of sprinkler systems for the below grade storage of flammable and combustible liquids in both new and existing facilities.

46
Q

GENERAL PRECAUTIONS AGAINST FIRE
COMBUBUSTIBLE LIQUID Bulk plants and terminals
Color coding
Fire protection systems shall be color-coded as follows:
1. Standpipe and/or yard hydrant systems
1.1 Piping, valve bodies and handles, hydrants and hydrant or hose houses - red with contrasting white bands.
1.2 Fire department connections:

A
  1. 1 - red with contrasting white bands.

1. 2– red

47
Q

GENERAL PRECAUTIONS AGAINST FIRE
COMBUBUSTIBLE LIQUID Bulk plants and terminals
Color coding
2. Automatic sprinkler systems (wet or dry)
2.1 Piping and valve bodies and handles
2.2 Fire department connections.

A
  1. 1 - red with contrasting bright green bands.

2. 2 - red with green caps

48
Q

GENERAL PRECAUTIONS AGCOMBUBUSTIBLE LIQUID Bulk plants and terminals
Color coding
AINST FIRE

  1. Nonautomatic sprinkler systems (including fog spray systems)
  2. 1 Piping and valve bodies and handles
  3. 2 Fire department connections.
A
  1. 1 - red with contrasting aluminum bands.

3. 2 - aluminum

49
Q

GENERAL PRECAUTIONS AGAINST FIRE
COMBUBUSTIBLE LIQUID Bulk plants and terminals
Color coding
4. Carbon dioxide extinguishing systems - Piping and valve bodies and handles

A
  • red with contrasting brown bands.
50
Q

GENERAL PRECAUTIONS AGAINST FIRE
COMBUBUSTIBLE LIQUID Bulk plants and terminals
Color coding
5. Steam extinguishing systems - Piping and valve bodies and handles.

A
  • red with contrasting black bands
51
Q

GENERAL PRECAUTIONS AGAINST FIRE
COMBUBUSTIBLE LIQUID Bulk plants and terminals
Color coding
6. Foam extinguishing systems
6.1 Piping, valve bodies and handles, hydrants and hydrant or hose houses
6.2 Fire department water connections
6.3 Fire department foam connections

A
  1. 1 - red with contrasting bright orange bands
  2. 2 - red, a durable sign that reads “WATER FOR FOAM SYSTEM.” shall be conspicuously posted immediately adjacent to such connections.
  3. 3 - red with contrasting bright orange band or caps. A durable sign that reads “CHEMICAL FOAM DIRECT TO TANKS” or “…% MECHANICAL FOAM SOLUTION DIRECT TO TANKS,” shall be conspicuously posted immediately adjacent to such connections.
52
Q

GENERAL PRECAUTIONS AGAINST FIRE
Under the administrative code, illegal storage and use of LPG is enforced with an immediate ______ and through the vendor or FDNY. Certain minor items can be enforced with an FDNY Summons or VO, which will be stated throughout this document.

A

summons … confiscation

53
Q

GENERAL PRECAUTIONS AGAINST FIRE
Number of containers requiring a permit
Pursuant to FC 105.6, an LPG permit shall be obtained for the storage, handling or use of more than ___ Standard Cubic Feet (SCF) of LPG.

A

400

54
Q

GENERAL PRECAUTIONS AGAINST FIRE

400 SCF is equal to approximately pounds of propane.

A

46

55
Q

GENERAL PRECAUTIONS AGAINST FIRE
Use in basement, pit or other area below grade
LPG containers shall not be used in a cellar, basement, pit or other area below grade where heavier-than-air gas might collect. LPG containers shall not be used in an above-grade under floor space or basement unless such location is provided with an approved means of ventilation. (FC 3803.2.1.1)
What are the 2 exceptions?
What is the additional exception regarding a 16.4 ounce container

A

Exceptions:

  1. Use with self-contained torch assemblies in accordance with FC3803.2.1.6 and the rules.
  2. Manhole operations in accordance with the rules

Additional exception as per 3RCNY 3809-01(j)(3)(C):
A single LPG container with a capacity not greater than 16.4 ounces may be used below grade for emergency indoor repairs, provided that the container is not left unattended.

56
Q

GENERAL PRECAUTIONS AGAINST FIRE
PROHIBITED STORAGE, HANDLING, AND USE OF LPG
Store, handle or use LPG in any container with a capacity greater than ___pounds.

A

100

57
Q

GENERAL PRECAUTIONS AGAINST FIRE
PROHIBITED STORAGE, HANDLING, AND USE OF LPG
Store, handle or use LPG without a permit when such storage, handling or use exceeds the quantities set forth in FC 105.6 and the rules.
What is the exception?

A

Exception: A permit is not required for stationary installations in R-3 occupancies.

58
Q

GENERAL PRECAUTIONS AGAINST FIRE

Are there any situations where storing LPG containers on the roof of any building may be permissible?

A

No

59
Q

GENERAL PRECAUTIONS AGAINST FIRE

Can someone handle or use on the roof of any building LPG containers with a capacity greater than 16.4? ounces,

A

Yes,

except as authorized by the Commissioner.(permit)

60
Q

GENERAL PRECAUTIONS AGAINST FIRE
Is there a situation where one can Store, handle or use LPG for a stationary LPG installation in any area where access to piped natural gas from a public utility is available?

A

No. Prohibited

61
Q

GENERAL PRECAUTIONS AGAINST FIRE
Storage within buildings accessible to the public
LPG containers constructed in accordance with the United States Department of Transportation (DOT) specifications with a maximum capacity of 16.4 ounces of LPG used in completely self-contained hand torches and similar devices are allowed to be stored for sale or displayed in a building accessible to the public. Buildings shall be protected by a sprinkler system in storage and display areas when quantities exceed permit amounts. The quantity of LPG shall not exceed ___ pounds.

A

200

62
Q

GENERAL PRECAUTIONS AGAINST FIRE
Storage within buildings not accessible to the public:
The quantity of LPG containers allowed in one storage location in a building not accessible to the public, such as an industrial building, shall not exceed a maximum capacity of ___ pounds of LPG. Where LPG containers are stored in more than one location on the same floor of a building, the storage areas shall be separated by a minimum of ___ feet. (FC 3809.10)
What is the exception?

A

300

Exception: Storage of LPG at construction sites shall be in accordance with the rules.

63
Q

GENERAL PRECAUTIONS AGAINST FIRE
Location of outdoor storage as per Fire Code
Outdoor storage, including storage of containers for sale and containers connected for use, shall be located not less than __ feet from building openings, 20 feet from any motor vehicle fuel dispenser and 10 feet from any combustible material and, as applicable, in accordance with the FC Table 3809.12. Outdoor storage of LPG shall be limited to not more than 400 pounds of LPG and shall be located at or above grade level. (FC 3809.12)
What is the exception?

A

20 build open….20 MV fuel disp…..10 combust mat
400 pounds

Exception: Storage of LPG at construction sites shall be in accordance with the rules.

64
Q

GENERAL PRECAUTIONS AGAINST FIRE
STATIONARY LPG INSTALLATIONS
Where are the containers stored? Indoor, outdoors, both?

A

All LPG containers connected for use in a stationary installation shall be stored outdoors.

65
Q

GENERAL PRECAUTIONS AGAINST FIRE
STATIONARY LPG INSTALLATIONS
Where on the piping must the shutoff be provided?
How many shutoffs are needed for appliances?

A
  • A single, accessible, safely-located, and conspicuously-marked shutoff valve shall be provided wherever LPG piping enters a building or structure
  • A single, accessible, safely-located and conspicuously-marked shutoff valve shall be provided for each appliance connected to a LPG container
66
Q

GENERAL PRECAUTIONS AGAINST FIRE
STATIONARY LPG INSTALLATIONS
A portable fire extinguisher with at least a 10-B: C rating shall be provided whenever LPG is connected for use. The maximum travel distance to the portable fire extinguisher shall be __ feet from the work location

A

30

67
Q

GENERAL PRECAUTIONS AGAINST FIRE
• Transportation plugs shall be installed on the LPG containers to secure gas-tight the outlet valve connection.
• LPG containers at all times shall be moved under the personal supervision of a-(holder of what)-At no time shall the containers be left unattended.

A

Certificate of Fitness holder.

68
Q

GENERAL PRECAUTIONS AGAINST FIRE
STATIONARY LPG INSTALLATIONS
How must a container over 20 lbs be moved?
What additional way can one 20 or less be moved?

A

LPG containers with a capacity of more than 20 pounds shall be moved to another floor of the building only by freight elevator, construction elevator, or passenger elevator when approved, and such elevator shall be occupied only by those persons engaged in moving the containers.
they may be moved in building stairwells if such stairwells are unoccupied.

69
Q

GENERAL PRECAUTIONS AGAINST FIRE
EMERGENCY INDOOR REPAIRS (3 RCNY 3809-01)
(subject to requirements) LPG equipment and containers may be used indoors, except in _____, for the purpose of performing emergency repairs.

A

an occupied place of public assembly

70
Q

GENERAL PRECAUTIONS AGAINST FIRE
EMERGENCY INDOOR REPAIRS (3 RCNY 3809-01)
LPG use at the work site shall be limited to ___ LPG containers, each with a capacity not greater than __ pounds
Greater than what size shall not be left unattended?

A

2
20
16.4 oz not left unattended

71
Q

GENERAL PRECAUTIONS AGAINST FIRE
EMERGENCY INDOOR REPAIRS (3 RCNY 3809-01)
All LPG use shall be under the personal supervision of a (holder of what) ; and
• All LPG containers shall be removed from inside the building at the end of the work day.

A

Certificate of Fitness holder

72
Q

GENERAL PRECAUTIONS AGAINST FIRE
EMERGENCY INDOOR REPAIRS (3 RCNY 3809-01)
Note: A single LPG container with a capacity not greater than __ ounces may be used below grade for emergency indoor repairs, provided that the container is not left unattended, as per 3 RCNY 3809-01(b)(2).
BY ORDER

A

16.4

73
Q

GENERAL PRECAUTIONS AGAINST FIRE
OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
Are voluntary systems subject to NYC fire code?

A

YES,

Voluntary systems must comply with maintenance and operation requirements in the New York City Fire Code.

74
Q

GENERAL PRECAUTIONS AGAINST FIRE
OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
Who is the person responsible for ensuring that proper safety precautions are taken when a fire protection system is out of service?

A

Designated impairment coordinator or the owner

75
Q

GENERAL PRECAUTIONS AGAINST FIRE
OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
A designated building representative who becomes aware of an out of service fire protection system shall immediately notify the owner or impairment coordinator. The owner/impairment coordinator shall notify the _________

A

Fire Department Borough Dispatcher.

Notification shall be made to the department whenever a standpipe system is or will be out of service for any period of time.

76
Q

GENERAL PRECAUTIONS AGAINST FIRE
OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
Notification that a sprinkler system or fire alarm system is or will be out of service shall be made to the department under the following circumstances:
1. The sprinkler system or fire alarm system is or will be out of service on _____ floor(s) of a building
2. With respect to a sprinkler system, the work or repairs cannot be completed, and the system restored to service, within ___ hours of the time the system was placed or went out of service
3. With respect to a fire alarm system, the work or repairs will require the fire alarm system to be out of service for more than ___ hours in any ___ hour period
4.–(how many)– other fire protection systems in the area in which a sprinkler of fire alarm system is out of service are or will also be out of service at the same time.

A
  1. 2 or more(more than one their words)
  2. 8 hours
  3. 8……24
  4. One or more
77
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
The owner, fire safety manager and/or impairment coordinator shall take the following actions whenever a standpipe system at a construction site is out of service:
1. (–when–) notify the department of any unplanned out-of-service condition.
2. Notify the department at least __ hours prior to any planned removal of the standpipe system from service.
3. Ensure that______ is continuously maintained while the standpipe system is out of service.
4.Repair the standpipe system and return it to service in compliance with the requirements of the New York City Fire Code and Building Code. The construction site may continue to be occupied, and construction, demolition or alteration activities may continue, pending such repair and restoration to service, except:________

A
  1. immediately
  2. 24
  3. a fire watch
  4. standpipe system, the conduct of certain construction, demolition or alteration activities would be imminently perilous to life or property; and that in no circumstance shall hot work
78
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
Any member who receives information about an out of service fire protection system shall immediately notify the Officer on duty.If the premise is in another company’s administrative district, the Officer notified shall make a journal entry and immediately telephone the Officer on duty in that company.
What does the admin co off. do upon notification/discovery?

A

Upon notification of an out of service fire protection system immediately investigate with members and apparatus.
Exception is a system shut down for scheduled maintenance.(following the rules otherwise)

79
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
In the case of a planned removal of service (inspection, testing, maintenance – completed within the end of a business day) for a sprinkler/standpipe system the officer should advise who?

A

surrounding units, the administrative Battalion and Division. Chief Officers should decide if any further action is required.

80
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
When a system is found to be out of service during an inspection or routine response the officer should notify who? Must it be at the scene or upon return to quarters?

A

request a Battalion Chief to respond, if the officer feels the response of a Battalion Chief is necessary
OR
the officer should notify the administrative Battalion Chief upon return to quarters.
Occupancies that have a large life hazard, large property value, or if sprinkler head replacement is considered a Battalion Chief shall be requested to respond.

81
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
When determining the parts of the system oos, who places/provides the tags?

A

Tag or tags are placed by the impairment coordinator or owner if an impairment coordinator is not designated by the owner. The FDNY does not provide or place these tags.
tag = oos
white blue disks also used

82
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
Enforcement: Violations, summonses, referrals
What are the options?

A

VO comply forthwith. Consider evacuation if no fire watch

83
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
Fireguards required. The fire watch required for an out-of-service standpipe system, sprinkler system or fire alarm system shall be maintained by one or more fireguards.
What’s the exception?
(Who? How Long? Square Feet?)

A

The impairment coordinator or other building staff trained and knowledgeable in conducting a fire watch may conduct a fire watch in lieu of a fire guard during the initial 4 hours of a planned removal from service, or after discovery of an unplanned out-of-service condition, provided that the floor or area in which the fire protection system is out of service does not exceed 50,000 square feet.

84
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
If an O.O.S. fire protection system has been discovered as the result of a routine inspection, complaint or Fire Department operation Issue what?

A

Serve an Immediate Summons for FAILURE TO NOTIFY.

85
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
If an alarm system has activated, however no access is available, conduct an exterior inspection. If there are no exterior indications of a fire condition notify the dispatcher to notify_________
What about sprinkler?

A

the alarm company

sprinkler. Ask dispatch if it reset. If no consider F.E. and notify dispatcher to notify alarm company.

86
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEM
Sprinkler with no alarm defective or shut down. Who can you notify to try and contact owner?
What if you F.E.?

A

Fire Marshals for potential notification to the responsible party if the system is confirmed to have a defect and/or was required to be shut down.

NYPD if FE

87
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
If a Standpipe system is discovered to be out of service during an operation/inspection and no responsible party is present notify the _____for potential notification to the responsible party. Notify the for security, if forcible entry was required.

A

Fire Marshals

NYPD

88
Q

GENERAL PRECAUTIONS AGAINST FIRE OUT OF SERVICE (OOS) FIRE PROTECTION SYSTEMS
If the out of service fire protection system is found in an occupied residential occupancy, however the owner, impairment coordinator, and/or responsible building staff are not available ask the Dispatcher to notify_____ .

A

OEM.