ASTM C143/C143M - Standard Test Method for Slump of Hydraulic Concrete Flashcards
Maximum aggregate size for slump testing is ___?
1.5 inches
Dimensions of the slump cone are?
4” diameter @ top
8” diameter @ bottom
12” high
Slump cone can be made of which materials?
Metal or Plastic
Metal slump cone thickness is ____ ?
Plastic slump cone thickness is ____?
.06 inches (1.5 mm) for metal
.125 inches (3 mm) for plastic
Sample of concrete for use in performing the slump test must be obtained in accordance with which ASTM practice?
ASTM C172
Slump cone is filled in ___ layers of equal ______?
3 layers of equal VOLUME
How deep should the bottom layer of concrete be?
How deep should the second layer of concrete be?
bottom layer = 2 5/8 inches
second layer = 6 1/8 inches
Interior of slump cone must be ________ prior to inserting concrete into the mold.
Dampened
If concrete drops below the top of the slump mold when rodding the final layer, what should you do?
Stop rodding, fill the cone with more of the sample and then continue rodding where you left off
Strike off the top of the cone with which device?
a - Tamping Rod
b - Strike-off bar
c - Strike-off plate
a - Tamping rod
Strike off the top of the cone using a ______ motion?
a - Sawing
b - Twisting
c - Both
c - Both
If a decided falling away, or shearing off of concrete from one side or portion of mass occurs, disregard the test and ____________________?
Make a new test from the same sample portion.
If two consecutive tests on a sample of concrete show a falling away or shearing off of a portion of the concrete from the mass of the specimen, the concrete probably lacks necessary _______ and ________ for the slump test to be applicable.
Plasticity
Cohesiveness
TRUE or FALSE:
When rodding the bottom layer, tamping rod must be angled to uniformly distribute the strokes
True
TRUE or FALSE:
Sides of the cone need to be tapped with open hand after consolidation of each later
False - Slump cone does not require tapping/striking