The required work space in front of a 480 volt motor control center is 03 ft. The motor control center is rated 1200 amps, is over 06 ft long, and is located in an equipment room. Personnel doors providing entrance and egress to the working space in front of the motor control center (MCC) are required to be equipped with panic hardware. Including the working space, what is the distance to the front of the MCC where doors with panic hardware are required?

A

28 ft.