ArcFlash 1 (20) Flashcards

1
Q

Our guidance?

A

3DI-E60G

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

IEEE guidance?

A

IEEE 1584

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The level of the hazard is defined by a ___?

A

calculated incident energy level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Incident energy is measured in terms of ___

A

Joules per square centimeter (J/cm2) or calories per square centimeter (cal/cm2).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is arc fault current?

A

Lower than bolted fault current due to arc impedance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How did we treat min fault current on Sherman-Temple MV?

A

Assumed as source contribution only (i.e. from UAT only without motor contribution).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How did we treat outgoing MV feeders on Sherman-Temple MV?

A

Did NOT cover faults on feeders. Work performed on cables would be done with breaker racked out.
With breaker racked out, any fault during operation can only be on the bus side (cable side is not hot).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How did we treat ground fault cases for MV switchgear buses on Sherman-Temple MV?

A

The ground fault current is limited to 400A therefore the analysis was not carried out for ground fault.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How did we treat min fault current on Sherman-Temple LV?

A

Assumed as source contribution only (i.e. from LC transformer only without motor contribution).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How can I tell if ETAP is reporting the arc-fault variation (85%)?

A

Diamond symbol, with note in lower left of the analysis report page for that particular bus.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the table in 70E for PPE Categories?

A

130.7 C E

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Do we use the PPE Categories defined in 70E?

A

No. 70E prohibits their use when you do an incident energy analysis.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the Restricted Approach Boundary?

A

The point at which a qualified person must wear rubber gloves or take other action to protect themselves.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the fast trip logic of a zone interlocking scheme?

A

Incomer 50 is enabled when no feeder has a fault indicated.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Do we ever consider energy based on failure of first protective device?

A

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

In ETAP, can you have a relay (for STAR and Arc Flash) with no associated breaker?

A

Yes

17
Q

Is the 85% factor for arcing current variation applicable to all voltages?

A

No. Only < 1000V per 1584 App. B.

18
Q

Where do the values for ‘working distance’ come from?

A

Standard table in 1584.

19
Q

Is the IE a function of working distance?

A

Yes

20
Q

Is the IE a function of the x (distance) factor?

A

Yes