1
Q

What is a category 1 appliance

A

Operates with a negative vent static pressure and a flue loss of no less than 17%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What does category 1 appliances consist of?

A

Draft hood equipped appliances, and fan assisted appliances for venting into B vents

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is a forced draft

A

A mechanical draft produced by a device upstream from the combustion zone

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is induced draft

A

A mechanical draft produced by a device DOWNSTREAM from the Comobution zone

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Natural draft is?

A

Any draft other than mechanical

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Another name for stack action, what is it?

A

Motive power, the suction in the flue caused by the products of combustion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the most biggest problem with venting

A

Condensation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

2 types of barometric draft controls

A

Single acting and double acting

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does a double acting barometric act do and how does it work

A

Swings 2 ways inwards and outwards, when it swings inwards, it lets diluation air in, if spillage occurs the damper swings outwards allowing combustion into the mech room rather then back to combustion zone

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does a single acting barometric damper do and how does it work

A

Only swings inward, allows dilution AIT into the vent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Barormatric damper can only be used appliances that have what?

A

Been certified by the manufacturer for such use

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How can venting gas appliances be accomplished.

A

Through convection or mechanical induction. Mechanical uses a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the total vent height

A

Min of 5’ft measured from the height of the draft hood or flue collar to where it vents outside

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is b vent made of

A

Inner lining is made of aluminum the outer wall is constructed of galvanized iron

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Maximum allowable flue gas temp for b vent

A

470f°

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Difference between b and bw vent

A

Bw is oval and has a smaller clearance
B vent is 1” BW is ½”

17
Q

2 types of chimneys

A

Factory built and field constructed.

18
Q

What is a vent

A

A vent for chimneys made of an inner liner of stainless steel and an outer layer of gal iron. 1” thick layer of mineral Fibre insulation between the 2 layers

19
Q

What is super A vent

A

The most commonly used style of manufactured chimneys. Inner and outer layer made of stainless steel and insulated with 2” fiber insulation.

20
Q

What is the recommended grade for BH venting

A

¼”

21
Q

What is 8.18.17 what venting does it apply to

A

A METAL vent connector shall not be installed without dips or sags

22
Q

What is a field built chimney

A

A chimney constructed of brick, stone, concrete, glazed tile or approved masonry units

23
Q

C.2.12

A
24
Q

What is a coaxial pipe

A

A single wall metal vent pipe installed inside another single wall metal air supply pipe.

25
Q

Min distance from grade for direct vent, what can you use to achieve that

A

12” a snorkel fitting

26
Q

A vent terminal cannot be located where?

A

Within 6ft of a mechanical air supply

27
Q

A vent shall not terminate within what of a service regulator

A

3ft

28
Q

The fresh air inlet connected to the return air duct is not considered a what

A

Mechanical air supply inlet