Anesthesia Systems Flashcards
3 Essential Components of a Breathing Circuit
Low resistance conduit for gas flow
Reservoir for Gas that meets inspiratory flow demand
Expiratory port or valve to vent excess gas
Requirements of a Breathing System (5)
- Deliver the gases from the machine or device to the alveoli in the same concentration as set and in the shortest possible time
- Effectively eliminate carbon dioxide
- Minimal apparatus dead space
- Low resistance to gas flow
- Allow rapid adjustment in gas concentration and flow rate
Effects of hypercarbia
Right shift on oxygen-hemoglobin dissociation curve
- Acidosis
- Vasodilation -> hypotension
- tachycardia
- increased ICP
The anatomic dead space in the circle system begins at
The Y Piece
Desirable Features in a Breathing System (8)
- Economy of fresh gas
- conservation of heat
- adequate humidification
- light weight
- convenience during use
- efficiency during spontaneous and controlled ventilation
- adaptability for adults, children, and mechanical ventilators
- proviso to reduce environmental pollution - safe disposal of waste gas
Higher FGF is associated with
less rebreathing in any circuit
Dead space increases
The chance of rebreathing CO2
Apparatus Dead space ends where
The inspiratory and expiratory gas streams diverge (Y-piece)
Apparatus dead space can be minimized by
separating the inspiratory and expiratory streams as close to the patient as possible (hence Y piece)
The concentration of inspired gas most closely resembles that delivered from the common gas outlet when
rebreathing is minimal or absent
Open classification =
no reservoir, no rebreathing (NO VALVES)
ex. sufflation, blow by, tenting, bronchoscopy port, nasal canula
Semi-Open classification =
Reservoir, no breathing
ex. some Maplesons, FGF dependent.
circle systems if FGF > MV (i.e. no rebreathing)
Semi-Closed classification =
Reservoir, partial rebreathing
Circle systems, FGF < MV
Closed classification =
Reservoir, complete rebreathing
FGF is minimal, APL closed.
Advantages of open systems
(i.e. blow-by, insufflation) - 7
Simple! Avoids direct patient contact No rebreathing of CO2 No reservoir bag No valves so less resistance and no chance of disconnection Good for peds Good for facial surgery
Disadvantages of Open Systems (blow-by, insufflation) - 5
No ability to assist or control ventilation
Requires high FGF to eliminate CO2 (especially with drapes/tenting)
No control of anesthetic depth/Fio2
Environmental pollution
Increased Fire Risk
Mapleson Components (4)
Connection point to a facemask or ETT
Reservoir Tubing
Fresh Gas inflow tubing
Expiratory pop-off valve / port
Best Measure of optimal FGF to prevent re-breathing
End tidal CO2
Fundamental ways that maplesons differ from circle systems
Bidirectional flow
Lack of CO2 absorber, elimination is dependent on FGF
Instances when maplesons are used - 5
Pediatrics
Transportation of patients
Procedural sedation
Weaning tracheal intubation
pre oxygenation during out of OR management
Three distinct functional groups of maplesons
A
BC
DEF
Structure of Mapleson A (Magill)
FGF is after reservoir bag,
Pop off valve is near face mask/ETT
FGF and pop valve are opposite each other
Best mapleson for Spontaneous Ventilation
All > Dogs > Can > Bite
With Mapleson A during Spontaneous Ventilation:
FGF = 1x MV then
there is no rebreathing
How to achieve no rebreathing with mapleson A during spontaneous ventilation
FGF. = 1 x MV
Steps of Spontaneous Ventilation with Mapleson A
- Pt takes a breath from reservoir (FGF) inhaling mostly FGF, emptying reservoir bag
- Pt expires alveolar gas/dead space gas into tubing. EXPIRATORY PAUSE
- During expiratory pause, FGF continues to flow, pressure in system is enough to open APL/pop off valve, gas escapes via valve, because this valve is closest to pt, the gas escaping is EXPIRED GAS.
Gas filling reservoir tubing is FGF.
Best Mapleson for Controlled Ventilation
Dog > Bites > Can > Ache
Steps of Controlled Ventilation with Mapleson A
With the APL valve closed, the anesthetist squeezes the reservoir bag to deliver a breath.
FGF is behind reservoir bag, gas is pushed towards pt.
Pt expires, alveolar gas/dead space gas mixes with FGF in reservoir bag.
Another breath given = not only FGF, but mixed gas. There will be rebreathing, extra pressure will allow mixed gas to leave via pop off valve.
To prevent rebreathing in Mapleson A with controlled ventilation
Much larger FGF, up to 20L/min
Disadvantages of Mapleson A (5)
- Inefficient for controlled ventilation (requires up to 20L/min to flush out mixed gas)
- Impractical design for operating room
- Proximal location of pop off valve makes scavenging difficult
- Difficult to adjust in head/neck surgery
- Heavy valve can dislodge small ETT
Structure of Mapleson B/C
FGF and pop off valve are located near each other and right near patient.
Mapleson C is used
For resuscitation and in patient transfer
Disadvantages of Mapleson B/C
FGF and pop off are so close to each other so mixing will always occur, requires huge FGF to wash out CO2.
Structure of Mapleson D
FGF is near patient,
pop off valve is closest to reservoir bag, they are far from each other as in A but D is the opposite of A.
Most efficient Mapleson for both spontaneous and controlled
Mapleson D
All Dogs Can Bite
Dog Bites Can Ache
Dogs are friends *
Steps of Spontaneous Ventilation with Mapleson D
- FGF is flowing closet to patient, so patient inhales mostly FGF,
- Pt exhales, expired gas mixes with FGF, goes down tube to reservoir bag.
EXPIRATORY PAUSE allows FGF to flush tubing, pop off valve opens when pressure is high enough, mixed gas escapes via pop off valve.
A higher FGF is still required to prevent rebreathing (2-3 x MV)
FGF required to prevent rebreathing in spontaneous ventilation with Mapleson D
2-3 x MV
Steps of Controlled Ventilation with Mapleson D
- FGF is flowing close to patient,
when reservoir is compressed to deliver a breath, pt receives breath that is mostly FGF. - Pt exhales, reservoir bag is mixed gas. No expiratory pause to flush gas, but when reservivr bag is compressed it pushes DISTAL FGF into pt, so less FGF overall is needed.
FGF for no rebreathing in controlled ventilation of Mapleson D
1 -2 x MV
Critical Difference between Spontaneous and Controlled Ventilation =
Expiratory Pause
Faster rate = shorter
expiratory pause, less ability for FGF to flush out expired air, greater risk for rebreathing
Conditions that increase CO2 production
fever, catabolic state, malignant hyperthermia
How to decreased CO2 with mapleson
Must increase rate and also FGF