Alarm Valves And Dry Pipe Valves Flashcards
What are the primary functions of Alarm Valves
-Act as check valves
-Initiate alarm signal
-Provides gauge port and signal switch ports
-Provides means of draining system
Will a paddle flow switch operate a WMG?
-No
What can the electrical signal from an alarm switch operate?
-Fans/exhaust
-Close doors
-Electric bell and buzzers, horns, and strobes
An audible alarm must be heard within how long of activating and alarm device?
5 minutes.
What is the monitor for the sprinkler system monitoring?
-Common Trouble
-Supervisory
-Alarm
Piping between the sprinkler system and the pressure actuated alarm initiating device shall be …
-Galvanized or non-corrosive
-not less than 3/8”
What is the minimum size drain for the alarm line piping’s restricted orifice to drain into?
1/4”
What types of sprinkler systems can a paddle flow switch be installed on?
Wet systems
What does the PS 10 switch typically monitor?
The Alarm line.
What does the PS 120 switch typically monitor?
System water pressure.
What does the PS 40 switch typically monitor?
System air pressure.
What are the three wet alarm valve seat types?
-Split or Groove Seat
-Pilot Port
-Divided Ring
Piping for WMG must be…
Minimum 3/4” and non-corrosive.
What is the max vertical distance a WMG can be from an alarm valve?
20’
What is the max horizontal distance a WMG can be from an alarm valve?
75’