50-300 VAC
Avoid contact
301-750VAC, WITHOUT Hold Order & NO Tools
1’ 1”
751V- 5kV, WITHOUT Hold Order & NO Tools
2’ 1”
15kV, WITHOUT Hold Order & NO Tools
2’ 2”
34.5kV, WITHOUT Hold Order & NO Tools
2’ 7”
69kV, WITHOUT Hold Order & NO Tools
3’ 4”
115kV, WITHOUT Hold Order & NO Tools
3’ 6”
138kV, WITHOUT Hold Order & NO Tools
4’ 0”
161kV, WITHOUT Hold Order & NO Tools
3’ 8”
230kV, WITHOUT Hold Order & NO Tools
6’ 2”
287kV, WITHOUT Hold Order & NO Tools
5’ 2”
345kV, WITHOUT Hold Order & NO Tools
5’ 11”
500kV (100’ design), WITHOUT Hold Order & NO Tools
8’ 8”
500kV (all others), WITHOUT Hold Order & NO Tools
9’ 10”
500kV Series Caps, WITHOUT Hold Order & NO Tools
11’ 3”
301V-750V, WITH Hold Order for Tools
1’ 1”
751V-5kV, WITH Hold Order for Tools
2’ 1”
15kV, WITH Hold Order for Tools
2’ 2”
34.5kV, WITH Hold Order for Tools
2’ 7”
69kV, WITH Hold Order for Tools
3’ 4”
115kV, WITH Hold Order for Tools
3’ 2”
138kV, WITH Hold Order for Tools
3’ 4”
161kV, WITH Hold Order for Tools
3’ 8”