6-2-3 Flashcards
The Working Load Limit (WLL) of any individual rigging component shall not be exceeded in any situation.
true
The three sags associated with a line conductor are stringing, maximum, and __?__.
final
Moving a conductor into a corner causes __?__.
sag and tension to increase
The formula used to calculate the vertical weight on a structure is __?__.
T times H over L…….or…….TxH/L
When pulling in a conductor, line tension __?__ when one-half of the sag is removed.
doubles
Line tension is normally less than __?__ for an aluminum conductor smaller than 3/0.
500lbs
Slings used on a 1000-pound transformer at a 60° angle will see __?__ each.
577lbs
When lifting a conductor, its weight doubles when the lowest point of sag reaches an adjacent structure.
true
The WLL (working load limit) is based on the actual breaking strength of the equipment and does not include a safety factor.
false
Chains that are safe to use as slings when doing line work will have each link marked with the letter __?__.
A
A knot may reduce the WLL of a rope by as much as __?__.
45-55%
A hand line may be used to hang a transformer that weighs 200 lbs or less.
false
Two things that must be known prior to rigging for a lift are the load weight and the __?__.
angle involved
When using a fiber rope, the shell of a block should be __?__ times the diameter of the rope.
8
An angle of 135° exerts less of a load on a block hook than an angle of 45°.
true