3.9. 8010 Flashcards
What is the role of the Fire Safety Watch (FSW)?
Continuously patrol all areas of the ship affected by the industrial work to inspect for smoke, fire, and for hazardous conditions or other conditions not compliant with the requirements of the 8010.
When can hot work be conducted?
After written notice for each job/separate area and a fire watch is posted.
How far must be clear of combustible material from the area of work to do hot work?
35 ft
How should a fire fighting system that is inop (and hose racks/reels are still onboard) be identified?
Should be labeled as inactive at each activation point
Portable fire extinguishers shall be installed so that the max travel distance from any interior point on the ship on the same level is no more than ____ ft.
50
In the case of hot work, extinguishers shall be located so that an agent can be applied to a fire within _____ seconds of discovery.
15
If Class B fire hazards are not present onboard, _____ are permitted as an alternative to AFFF extinguishers.
Pressurized water extinguishers
Can fire hoses be used as a complement or substitute for portable extinguishers?
Yes, but only with prior approval from the CO
What is required to be at a drydock fire hose station?
- fire plug
- constantly available water source at 95 gpm, 60 psi
- 100 ft of pre-connected hose
- 1 1/2” nozzle rated for 125 gpm at 100 psi
_____ is an acceptable extinguishing agent to utilize for Special Hull Treatment (SHT) fires in the dry dock.
Seawater
What are the shipboard fire reporting device requirements?
(1) fire alarm pull box,
(2) a direct line telephone, or,
(3) a device combining both.
Where must fire reporting devices be located on ships?
(1) In each fire zone
(2) at least every 100 feet of ship’s length on decks that transverse greater than 100 feet of ship’s length
(3) placed on alternating sides of the deck, and,
(4) at a junction with athwartship pways where practical
Where should fire reporting devices be located for shipboard superstructures?
(1) Each level in each fire zone
(2) a reporting device is within 100 ft of any part of the level
For decks/platforms below the Main Deck less than 100 ft of ship’s length, what are the fire reporting device requirements?
Located in each space, within 10 feet of all exit ladders
Where should fire reporting devices be placed relative to tanks open for maintenance?
Within 10 feet