What monitors and and controls the transfer system components?
control console
Within the Fill and Transfer system the transfer pumps are rated at ________ gpm at _______ psi discharge pressure.
200
50
Up to how many transfer pumps may be used when transferring between storage tanks?
3
In transfer piping, how many locations are cross-connected to form loops?
4
The suction header cross connect has a butterfly cutout valve and _____________.
pipe blind (spectacle flange)
How many tanks may be filled from any filling station?
All
How many tanks per manifold?
5
What is the maximum filling rate of a JP-5 tank?
500 gpm
What receives fuel from the transfer pumps and discharges the purified fuel to the service tanks?
Centrifugal Purifiers
When filling service tanks, close fill valves at what percentage of capacity?
95%
When operating the JP-5 Fill and Transfer System the number of tanks open must be sufficient to limit flow to _________ per tank and minimum of ___________ tanks.
500 gpm
six
When stripping stowage tanks take ________ samples.
visual
Only ______ transfer pump may be aligned to each purifier when transferring to the service system.
one
Two purifiers installed in each pumproom (forward and aft), each having a capacity of ________ gpm.
200
How many filling stations on the main deck provide for receiving and offloading JP-5?
Five