31000 Basic Fire Alarm Systems Flashcards
What systems are required to have secondary power capable of operating the system for 24 hours in normal operation?
Local System, Household System, Central Station System, Proprietary Station System
What is the smallest conductor size allowed for shunt type auxiliary circuits?
14 AWG
What type of fire alarm system requires placarding?
Central Station System
What device has a listed spacing?
Heat Detectors
A fire alarm system which serves contiguous or noncontiguous properties under 1 ownership is what type?
Proprietary System
An initiating device which is destroyed as a result if it operation is what type?
Nonrestorable
The delay from operation of an initiating device until the activation of a fire safety function shat not exceed ____ seconds?
10 Seconds
What documentation shall be provided to the building owner upon completion of the installation?
Owners and Installation Manuals, Record Copy of the the specific Software, Record Drawings
What detector operates on the principles of light obstruction?
Photoelectric and Beam Detectors
According to NFP72, the minimum mounting height for the pull stations shall be?
42” to the actuator
Which of the following requirements is true?
A. Each floor if the building shall be zoned
B. All unoccupied areas shall be zoned
C. Line type and spot type heat detectors shall be zoned separately
A. Each floor if the building shall be zoned
What is an example of a fire safety function?
Elevator Recall
In the event of power failure, the secondary power supply shall provide power to the system within ___ seconds?
10 Seconds
Fire alarm signals shall take precedence over all other signals. What type of signal is second in the precedence hierarchy?
Supervisory
What does the asterisk (*) designate on the NFPA 72?
a. Explanatory information follows in the appendix
b. An exception to the requirement follows
c. A change in information from the last edition of the code
d. See UL standards for detailed explanations
a. Explanatory information follows in the appendix
A single-owner or single-user protected premises on a continuous plot of ground, including any buildings thereon, that is not separated by a public thoroughfare, transportation right-of-way, property owned or used by others, or body of water not under the same ownership.
Contiguous Property
An owner or single-user protected premises on a continuous where two or more protected premises,controlled by the same owner or user, are separated by a public thoroughfare, body of water, transportation right-of-way or property owned by others
Non-contiguous Property