302 Introduction to grounding and bonding Flashcards
The human body is a good conductor because it is mostly salt water.
a. True
b. False
a. True
The symbol used for impedance in an electrical formula is ____.
a. I
b. R
c. Z
d. Ohm’s sign
e. X
c. Z
Potential difference refers to which of the following?
a.  voltage
b. Resistance
c. Shock hazard of AC circuits as compared to DC circuits
d. Shock hazard associated with different grounding methods
a. Voltage
O’Reilly’s first rule of electrical installations is to make them _____.
a. Work
b. Safe
b. Safe
Electrical fault cause all of the following types of stresses, except ______.
a. Thermal
b. Seismic
c. Magnetic 
b. Seismic
Potential difference is a value measured in Ohm’s.
a. True
b. False
b. False
Total opposition to current flow in an alternating current (AC) circuit is _____.
a. Impedance
b. Reactance
c. Resistance
d. None of these
a. Impedance
The point of division Of a line and load is located in the ______.
a. Load side of the meter base
b. Customer side of the service head
c. Service point
d. Overcurrent devices in the service disconnect means
d. Overcurrent devices in the service disconnecting means
A(n) _____ Conductor carries circuit current in normal operation.
a. Equipment grounding
b. Neutral
c. Grounding electrode
d. None of these
b. Neutral
If the resistance of the body is 100 ohms, how much current would pass through the body when connected to a 120 Volt circuit?
a. 12 A
b. 10 mA
c. 10 Amps
d. 1.2 amps
d. 1.2 amps
If a fault occurs at point III In figure 301.01, It is on the ______ side of the service.
a. Line
b. Load
b. Load
If a fault occurs at point IV In figure 301.01, it is on the ____ Side of the service.
a. Line
b. Load
b. Load
Which of the following are considered to be current carrying conductors?
I. Neutral conductor. II. Ungrounded conductor.  III. Grounding conductor
a. I & II only
b. II only
c. I & III only
d. II & III only
e. I only
a. I & II only
When a piece of equipment is connected to ground, it meets the definition for ____.
a. Insulated
b. Guarded
c. Isolated
d. Grounded
d. Grounded
If two points in a circuit have a voltage between them but are then bonded together with a conductive jumper (a wire for example), There is essentially no longer ____ between them.
a. A difference of potential
b. A voltage
c. Both a & b
d. Neither a nor b
c. Both a & b
A solidly grounded system is one where one of the current-carrying conductors is intentionally connected to the Earth.
a. True
b. False
a. True
Which of the following is not an example of a solidly grounded system?
a. 120/240-volt, three phase, four wire
b. 480 V, three phase, three wire
c. 120/240 V, single-phase, 3 wire
d. 120/208 V, three phase, four wire
b. 480 V, three phase, three wire
Potential difference is a value measured in ____.
a. Amps
b. Ohms
c. Volts
d. Watts
c. Volts
A five wire system consists of grounded, three phase system and includes one insulated ground and one insulated grounding conductor.
a. True
b. False

a. True
A solidly grounded system is a system in which one of the circuit conductors is grounded. This conductor _____ carry Current during normal circuit operations.
a. Does not
b. Does
a. Does not
The definition of an equipment grounding conductor in the NEC generally covers many different concepts and parts of a grounding system.
a. True
b. False 
a. True
In terms of grounding, the earth is considered to represent _____.
a. zero potential
b. Infinite impedance
c. A natural battery
d. Negative polarity
a. Zero potential
Most common configuration for a grounded, three phase, AC distribution system is for wire, center grounded (also called “wye connected”). The code requirements for identification of a grounded conductor are provided in section _______.
a. 250.119
b. 200.6(A)
b. 200.6(A)
The abbreviation or symbol used for the unit of measure for impedance is _____.
a. VA
b. Z
c. W
d. A
e. V
b. Z