3-5-2 Reclosers and Sectionalizers Flashcards
A recloser is most often set to trip out at __?__ times its rating.
2
The part of a recloser that senses a fault is the __?__.
solenoid coil
A hydraulic recloser cannot interrupt nominal load current.
False
The acronym SCADA stands for __?__ and data acquisition.
Supervisory Control
The recloser which has a cold-load pickup feature is the __?__ recloser.
electronic
The electronic recloser can be closed manually if it does not have a low voltage supply.
False
Sectionalizers are not designed to interrupt __?__.
fault current
Sectionalizers normally have a non-reclose handle which can be used as a safety device when working in the area the sectionalizer protects.
False
Type H reclosers contain coils that vary in size from 5 to __?__ amps.
50
On type H reclosers, the fastest curve is the __?__ curve.
A
The two types of faults that will cause a recloser to operate are temporary and permanent.
True
The type L reclosers vary in size from __?__ to __?__ amps.
25 to 280
Most utilities and operating companies have standards of operation for their reclosers, setting them at __?__ fast operations and __?__ slow operations.
two, two
Single-phase reclosers are of the __?__ and __?__ -type.
H / L
A single-phase recloser rated at 14.4kV can be operated on an electrical system up to that voltage without making any electrical adjustments.
True