2016 CMC Chapter 3 : Sections Flashcards

1
Q

Equipment of appliance shall be approved by the AHJ for safe use or comply with applicable nationally recognized standards as evidenced by the _______ and ________ of an approved agency. A list of accepted standards is included in Chapter 17. Defective materials or parts shall be replaced in such a manner as not to invalidate an approval.

A

Listing and Labeling

2016 CMC 301.2
General - Approval

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Installers shall furnish satisfactory evidence that the appliance is constructed in accordance with the requirements of this code. The permanently attached label of an ________ ______ shall be permitted to be accepted as such evidence.

A

Approved Agency

2016 CMC 301.3
General - Design of Equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Equipment regulated by this code requiring electrical connections or more than __ ____ shall have positive means of disconnect adjacent to and in sight from the equipment served.

A

50 Volts

2016 CMC 301.4
General - Electrical Connections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

A 120 volt receptacle shall be located within __ ___ of the equipment for service and maintenance purposes. The receptacle need not be located on the same level as the equipment.

A

25 Feet

2016 CMC 301.4
General - Electrical Connections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Low-voltage wiring of 50 volts or less within a structure shall be installed in a manner to prevent _______ ______.

A

physical damage

2016 CMC 301.4
General - Electrical Connections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Electrical wiring, controls, and connections to equipment and appliances regulated by this code shall be in accordance with ____ __.

A

NFPA 70

2016 CMC 301.4
General - Electrical Connections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The tank, piping, and valves for appliances burning oil shall be installed in accordance with ____ __.

A

NFPA 31

2016 CMC 301.5
General - Oil-Burning Appliances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A _____ _____ shall be provided around exposed flywheels, fans, pulleys, belts, and moving machinery that are portions of a heating, ventilation, or refrigerating system.

A

Metal guard

2016 CMC 301.6
General - Personnel Protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

2016 CMC 302

A

Materials - Standards and Alterations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Listed pipe, pipe fittings, appliances, appurtenances, equipment, materials, and devices used in a mechanical system shall be ______ or _______ (third-party certified) by a _______ ______ (accredited conformity assessment body) and shall comply with the approved applicable recognized standards referenced in this code, and shall be free from defects. Unless otherwise provided for in this code, materials, appurtenances, or devices used or entering into the construction of mechanical systems, or part thereof, shall be submitted to the AHJ for approval.

A

Listed or Labeled by a Listing Agency

2016 CMC 302.1
Minimum Standards

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

2016 CMC 302.2

A

Alternate Materials and Methods of Construction Equivalency

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

2016 CMC 302.3

A

Alternative Engineered Design

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Central heating furnaces and boilers installed in closets or alcoves shall be listed for such installation. Central heating furnaces not listed for closet or alcove installation shall be installed in a room or space having a volume not less than __ times the total volume of the furnace

A

12 times - with exceptions

2016 CMC 303.2
Closets or Alcove Installation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Central heating boilers not listed for closet or alcove installation shall be installed in a room or space having a volume __ times the volume of the boiler.

A

16 times - with exceptions

2016 CMC 303.2
Closets or Alcove Installation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Except as otherwise provided in this code, unlisted appliances shall be installed in accordance with the ________ _________ __________ and with the standard clearances from combustibles in accordance with Section 303.10 or Section 303.10.1

A

Manufacturer’s Installation Instructions

2016 CMC 303.3
Installation - Unlisted Appliances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Clearances of listed appliances from combustible materials shall be as specified in the listing or on the ______ ______.

A

Rating plate

2016 CMC 303.1
Installation - Listed Appliances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Movement of appliances with casters shall be limited by a restraining device installed in accordance with the ________ and appliance manufacturer’s installation instructions.

A

Connector

2016 CMC 303.5
Installation - Movement

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Where more than one heating, cooling, ventilating, or refrigerating system is installed on the roof of a building, it shall be ___________ __________ as to the area or space served by the equipment

A

Permanently Identified

2016 CMC 303.6
Installation - Identification of Equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Equipment and appliances on roofs requiring an external source of electrical power for its operation shall be provided with the following;
1. A readily accessible electrical disconnecting means within _____ of the equipment and appliance that will completely de-energize the equipment and appliance.

A

within sight

2016 CMC 303.8.5
Equipment and Appliances on Roofs - Electrical Power.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

Equipment and appliances on roofs requiring an external source of electrical power for its operation shall be provided with the following;
2. A 120-VAC grounding-type ________ ______ on the roof adjacent to the equipment and appliance. The ________ ______ shall be on the supply side of the disconnect switch. [NFPA 54:9.4.2.3]

A

Receptacle Outlet

2016 CMC 303.8.5
Equipment and Appliances on Roofs - Electrical Power.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

2016 CMC 304.0

A

Accessibility for Service

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Appliances shall be located with respect to building construction and other equipment so as to permit access to the appliance. Unless otherwise specified, not less than __ inches in depth, width, and height of working space shall be provided.

A

30 inches

2016 CMC 304.1
Accessibility for Service - General

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

2016 CMC 305.0

A

Location

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Where a water heater is located in an attic, in or on an attic-ceiling assembly, floor-ceiling assembly, or floor-subfloor assembly where damage results from a leaking water heater, a watertight pan of corrosion-resistant materials shall be installed beneath the water heater with not less than ¾ of an inch diameter drain to an approved location. such pan shall be not less than __ inches in depth.

A

1 ½ inches

2016 CMC 305.4
Location - Drainage Pan

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

2016 CMC 306.0

A

Automatic Control Devices

26
Q

Forced-air and gravity-type warm air furnaces shall be equipped with a listed ___ ______ ___________ _____ _______ that cannot be set for temperatures exceeding 250°F. Such controls shall be located in the bonnet or plenum, within 2 feet of the discharge side of the heating element of gravity furnaces or in accordance with the conditions of listing.

A

Air Outlet Temperature Limit Control

2016 CMC 306.1
Automatic Control Devices - General (Exception)

27
Q

Electric duct heaters shall be equipped with an approved automatic reset air outlet temperature limit control that will limit the outlet air temperature to not exceed 200°F. The electric elements of the heater shall be equipped with _______ _____ or a manual reset temperature limit control that will prevent outlet air temperature in excess of 250°F.

A

Fusible Links

2016 CMC 306.1
Automatic Control Devices - General (Exception)

28
Q

2016 CMC 307.0

A

Labeling

29
Q

2016 CMC 310.0

A

Condensate Wastes and Controls

30
Q

Condensate or wastewater shall not drain over a ______ ___.

A

Public Way

2016 CMC 310.1 Condensate Disposal

31
Q

Where approved by ___ ___, condensate pumps shall be installed ins accordance with the manufacturer’s installation instructions.

A

the AHJ

2016 CMC 310.1.1 Condensate Pumps

32
Q

When condensate pumps are used, each condensing unit shall be provided with a separate ____ and interlocked with the equipment to prevent the equipment from operating during a failure.

A

Sump

2016 CMC 310.1.1 Condensate Pumps

33
Q

Where the condensate waste from air-conditioned coils discharges by direct connection to a lavatory tailpiece or to an approved accessible inlet on a bathtub overflow, the connection shall …

A

…be located in the area controlled by the same person controlling the air-conditioned space.

2016 CMC 310.6 Condensate Waste From Air-Conditioning Coils

34
Q

2016 CMC 311.0

A

Heating or Cooling Air Systems

35
Q

A heating or cooling air system shall be proved with ______ ___, _______ ___. or both.

A

return air, outside air

2016 CMC 311.1 Source

36
Q

Media-type air filters shall comply with __ ___.

A

UL 900.

Exceptions;

(1) Systems serving single guest rooms or dwelling units shall not require a listed filter.
(2) Air filters used in listed appliances and in accordance with the manufacturer’s instructions.

2016 CMC 311.2 Air Filters

37
Q

2016 CMC 311.3

A

Heating or Cooling Air Systems, Prohibited Sources for Outside or Return Air.

38
Q

Outside or return air for a heating or cooling air system shall not be taken from less than __ feet in distance from an appliance vent outlet, a vent opening of a plumbing drainage system, or the discharge outlet of an exhaust fan, unless the outlet is 3 feet above the outside-air inlet.

A

10 feet

2016 CMC 311.3 (1) Prohibited Sources

39
Q

Outside or return air for a heating or cooling air system shall not be taken from less than __ feet above the surface of an abutting public way, sidewalk, street,alley, or driveway.

A

10 feet

2016 CMC 311.3 (2) Prohibited Sources

40
Q

______ ___ from one dwelling unit shall not discharge into another dwelling unit through the heating or cooling air system.

A

Return Air

2016 CMC 311.4 Return Air Limitations

41
Q

Outside or return air for a heating or cooling air system shall not be taken from an area, the volume of which is less than 25 percent of the entire volume served by such system, unless there is an opening to an area the volume of which is equal to 25 percent of the entire volume served.
Exceptions: Such opening where used for a heating or cooling air system in a dwelling unit shall be permitted to be reduced to not less than 50 percent of the required area, provided the balance of the required return air is taken from a room or hall having not less than three doors leading to other rooms served by the furnace.

A

2016 CMC 311.3 (4)

Heating or Cooling Air Systems - Prohibited Sources

42
Q

Outside or return air for a heating or cooling air system shall not be taken from the following locations;
A ______, ________, ______ ____, or _______.

A

A closet, bathroom, toilet room, or kitchen.

2016 CMC 311.3 (5)
Heating or Cooling Air Systems - Prohibited Sources

43
Q

A minimum of ___ boilers shall be provided. the arrangement of boilers shall be based on the capacity and capability of a boiler or boilers to operate all systems during-periods of breakdown or maintenance of any one boiler.

A

Two

2016 CMC 319.1
Steam and Hot-Water Systems -
Requirements for Hospitals and Optional Services Provided in Correctional treatment Centers [OSHPD 1 and 4]

44
Q

Boiler systems providing space heating shall be designed to maintain a minimum temperature of __°F in general patient areas and the temperatures specified in Table 320.0 for sensitive areas during periods of breakdown or maintenance of any one boiler. Winter design temperature shall be based on the Median of Extremes shown by the 1982 ASHRAE Climatic Data fro Region X and ASHRAE 1994 Supplement to Climatic Data for Region X.

A

60°F

2016 CMC 319.1.3
Steam and Hot-Water Systems -
Requirements for Hospitals and Optional Services Provided in Correctional treatment Centers [OSHPD 1 and 4]

45
Q

Boilers shall have the capacity, based upon the ____ _______ published by the Hydronics Institute or another acceptable national standard to supply the normal operating requirements of all connected systems and equipment.

A

Rest Ratings

2016 CMC 319.1
Steam and Hot-Water Systems -
Requirements for Hospitals and Optional Services Provided in Correctional treatment Centers [OSHPD 1 and 4]

46
Q

Boiler feed pumps, condensate return pumps, fuel oil pumps, and heating circulating pumps shall be connected and installed to provide _______ service in the event of pump failure. Installation of duplex pumps or provision of a spare pump will meet this requirement.

A

Standby

2016 CMC 319.4
Steam and Hot-Water Systems -
Requirements for Hospitals and Optional Services Provided in Correctional treatment Centers [OSHPD 1 and 4]

47
Q

2016 CMC 320.0

A

Air Conditioning and Heating Systems

48
Q

The systems shall be designed to provide the temperatures and relative humidity for sensitive areas or rooms shown in Table 320.0. When outdoor humidity and internal moisture sources are not sufficient to meet the requirements of Table 320.0, humidification shall be provided by means of the ______-___ ________ ___-_______ systems. Temperatures shall be individually controlled for each operating and delivery room.

A

health-care facility air-handling systems

2016 CMC 320.1.1
Air Conditioning and Heating Systems -
Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers. [OSHPD 1 and 4]

49
Q

Burn unit patient rooms that require humidifiers to comply with Table 320.0 shall be provided with individual humidity control. All humidifiers shall use ___ _____. Humidifiers shall be located within air handling systems or ductwork to avoid moisture accumulation in down-stream components, including filters and insulation.

A

dry steam.

2016 CMC 320.1.1
Air Conditioning and Heating Systems -
Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers. [OSHPD 1 and 4]

50
Q

For occupied areas not shown in Table 320.0, heating systems shall be designed to provide __°F to __°F based on the Climatic Design Data in the most recent version of ASHRAE Handbook-Fundamentals. The systems shall be thermostatically controlled with appropriate zoning to achieve the above conditions.

A

70°F to 75°F

2016 CMC 320.1.2
Air Conditioning and Heating Systems -
Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers. [OSHPD 1 and 4]

51
Q

For occupied areas not shown in Table 320.0, cooling systems shall be designed to provide __°F maximum based on the 0.4 percent summer design dry bulb temperatures shown by the Climatic Design Data in the most recent version of ASHRAE Handbook-Fundamentals. The systems shall be thermostatically controlled with appropriate zoning to achieve the above conditions.

A

75°F

2016 CMC 320.1.3
Air Conditioning and Heating Systems -
Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers. [OSHPD 1 and 4]

52
Q

During periods of power outages essential electrical power shall be provided for;
321.1
(Does not apply to OSHPD 3 surgical clinic.) All heating equipment necessary to maintain a minimum temperature of 60°F in patient areas which are not specified in Table 320.0.
Section -

A

321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3 (Surgical Clinics only) and 4]

53
Q

During periods of power outages essential electrical power shall be provided for;
321.2
All heating equipment necessary to maintain the minimum temperatures for sensitive ares as specified in Table 320.0

A

321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3 (Surgical Clinics only) and 4]

54
Q

During periods of power outages essential electrical power shall be provided for;
321.3
Equipment necessary for humidification of the areas listed in Table 320.0.

A

321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3 (Surgical Clinics only) and 4]

55
Q

During periods of power outages essential electrical power shall be provided for;
321.4
All supply, return, and exhaust fans required to maintain the positive and negative air balances as required in Table 4-A

A

321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3 (Surgical Clinics only) and 4]

56
Q

During periods of power outages essential electrical power shall be provided for;
321.5
All control components and control systems necessary for the normal operation of equipment required to have essential electrical power.

A

321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3 (Surgical Clinics only) and 4]

57
Q

During periods of power outages essential electrical power shall be provided for;
321.6
Alarms for airborne infection isolation rooms and protective environment rooms.

A

321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3 (Surgical Clinics only) and 4]

58
Q

Heating, cooling, and relative humidity LD requirements for sensitive areas or rooms can be found in…

A

2016 CMC Table 320.0

59
Q

National Fuel Gas Code

A

NFPA 54

60
Q

Table 313.3

A

Hangers and Supports

61
Q

Table 303.10.1

A

Reduction of Clearances with Specified Forms of Protection. [NFPA 54: Table 10.2.3]

62
Q

Reduction of clearances from appliance, connectors and single-wall metal pipe can be found in…

A

Table 303.10.1

Reduction of Clearances with Specified Forms of Protection. [NFPA 54: Table 10.2.3]