118 Flashcards
- According to the APM, what size and type of rope is required for lowering a person from a pole?
Workload rating equal to 1/2”
APM 1022
What are the basic steps in pole top rescue?
- Clear victim of imminent danger.
- Administer first aid.
- Lower the victim to the ground.
Reference: APM Rule 1022.a
- What is the purpose of a breakaway reel?
This reel is designed to recover overhead, as well as underground, conductors that are to be salvaged.
Reference: Rigging Standards Manual, p. 79
What are the maximum fault duties for the three sizes of grounds used on distribution
voltages?
112 =9,000 A
2/0 =18,000 A
4/0 = 30,000 A
Reference: Overhead Grounding Manual, Table 3-1
What size grounds should be used on 1/0 ACSR circuit with a fault duty of 10,000 A?
For aluminum conductors 1/0 AWG or smaller, then #2 AWG copper grounds may be used for grounding, regardless of source voltage and fault current duty.
OGM Table 3-1
How does a lineman find the fault duty for a particular circuit?
Refer to the Protection Engineering website.
Reference: Overhead Grounding Manual, 2.3.2
How often is grounding equipment tested?
Every 2 years, through GARP.
Reference: Overhead Grounding Manual, 5.1
Under what circumstance is it required that the substation ground grid be used as the grounding medium?
The substation ground grid shall be used as a ground medium when grounding ‘Within 40 feet of the substation ground grid and proper locations shall be selected for routing and attaching grounds to the substation ground grid,
Reference: Overhead Grounding Manual, 3.6.2
What size conductors are typically used in single-phase lighting secondaries?
Certain sizes of conductors are most commonly used for lighting secondaries: 1/0 aluminum or #2 copper in all residential areas except those designed for minimum service, and 4/0 aluminum or 2/0 copper where the initial installation requires transformers larger than 25 kVA.
Reference: DOH, 400.1.0
The APM prescribes two safety guidelines that must be performed prior to working on a transformer with banked secondaries. What are they?
\Nhere secondaries of transformers are banked or there is a posslbility of a backfeed, the transformer secondary leads shai! be disconnected in addition to pulling primary fuses before any work is done on a transformer.
APM 217
What are the minimum acceptable Megger test values for accepting both new and old
transformers, prior to installation?
New: >999 MO. Old: >500 MO.
Why are Megger checks performed on transformers?
The Megger measures the effectiveness of a transformer’s electrical insulation.
What is special about Megger and TTR tests on 6.9 kV/9.5 kV (0-Ground} 240/120 V, non- fused, single-phase looped BURD transformers with three low-voltage bushings?
No Megger test is possible since both windings and the tank are all connected.
Reference: Megger and TTR Reference Manual for Testing Distribution Transformers, Megger and TTR Testing of Specific Transformer Types 5.0
. List two examples of transformer defects that may be detected with TTR and Megger checks
A transformer can become defective in several ways. Broken insulation or shifting components can lead to shorts either within windings or between leads and the case or between windings and the core. Any one of the many connections inside the transformer can open up due to improper crimping or brazing or improperly secured fasteners. Leads may be routed incorrectiy during the assembly process resulting in incorrect polarity.
Each of the defects just described may be detected using the Megger and TTR
What five precautions must be observed before and/or during Megger testing of a transformer?
Isolate the Transformer.
Watch out for Shocks
Make Good Electrical Contact with the Terminals Vent the Transformer
Understand the Transformer Nameplate
Reference: Megger and TIR Reference Manuai for Testing Distribution Transformers,
Why are TTR checks performed on distribution transformers, priorto installation?
The function of this meter is to identify defects that would show up as anomalies in the turns ratio of the transformer
- Describe what a transformers polarity is.
The relative instantaneous direction of current through the coils of a transformer
2nd step transformer theory manual
What is the maximum acceptable level of error (percentage) when performing a TIR check on a.transformer?
IEEE standards allow manufacturers to build transformers with percentage errors up to 0.5 %. This is the number that the TIR uses to determine whether the transformer being tested passes or fails.
Reference: Megger and TIR Reference Manual for Testing Distribution Transformers, TIRS.O
What is the purpose of a transformer tap changer? How does it work?
Tap changers allow the transformer to be “fine tuned” so that the output of the transformer remains at the rated low voltage despite a higher- or lower-system voltage. This “fine tuning” is accomplished by increasing or decreasing the effective number of turns in the high-voltage winding.
Reference: Megger and TIR Reference Manual for Testing Distribution Transformers,
. Is it permissible to operate a transformer’s tap changer while it is energized or part of a bank?
No. a transformer, and its bank, must be off line.
Reference: 2nd Step Transformer Theory Training Manual
Concerning poie framing and crossarm construction on a rural pole, when are V-braces required?
Use V-braces for wire size larger than #2 copper and 1/0 .ASCR.
DOH Figure DC 500
is it permissible to reduce the required 6-foot clearance between secondary conductors and communications lines? lf so, how?
Yes, with the installation of a guard arm.
Reference: DOH, Figure DC 200-1 Note 2
What is the requirement for placing HIGH VOLTAGE signs on wood poles with crossarm(s) supporting the lowest level of the line conductors energized in excess of 750 V?
HIGH VOLTAGE signs are placed to encircie the pole so that the top of the sign is located
nomore than 40 inches below the lowest level of the line conductors energized in excess
of 750 V. ~
Reference: OOH, PO 12.0.2 3.1
- What are the ampacities for each of the following conductor types/sizes?
#4 ACSR - 160 1/0 ACSR - 280 4/0 ACSR - 415 336 ACSR - 605 653 ACSR - 920 #4AT-110 #2 AT - 145 1/0 AT - 190 4/0 AT - 300 1/0 AQ - 180 4-0 AQ - 275 DOH CO - 106
What is the WLL of a stabilizer (silver) gin?
2000lbs
Rigging Standards Manual figure 205
What is a USA, and when would it be required? What company provides SCE with USA service?
USA= Underground Service Alert. USA information is provided to SCE by DigAlert.
State of California Government Code 4216 mandates that anyone doing excavation work shall call at least two working days prior to commencement of any excavation. lf you are performing this type of work in California or ~Nevada, please call Underground Service Alert at (811) or (800} 227-2600..
Reference: Electrical Service Requirements, ER-14.0
What is the secondarv’ climbing space dimensions for the following?
a) Arm construction
b) Triplex construction
c) Rack construction
a) 30 inches square
b) 30inchessquare
c) Diameter of pole+ Su (2Y2” and 2 Yz’’ on each side) x 30” deep x 38” across the backside.
Reference: DOH, Figures DC 100-1, 100-4, and 320-i
When using a hand hoist, is it acceptable to use the chain and hook in a choker configuration? Why or why not?
No. The hook will break under stress.
Reference: Rigging Standards Manual, Figure 147
What are the three basic nylon siing hitches?
Straight Pull
Choker Hjtch
Basket Hitch
Reference: Rigging Standards Manuai, Figure 84
What is the correct type of wire used in under the arm fiber?
insulated conductors.
Reference: DOH, DC 323 and G,O. 95, S4.6C2
What are the clearance requirements for a streetlight electrolier and secondary
conductors?
No specified clearance is required for supply service drops 0-750 V if the streetlight pole is non-climbable and the cable is suitably insulated and mechanically protected. See G.O. 95, Rule #54-8-D (1)
Reference: DOH, Figure SL 106-1
What is the maximum height at point of attachment for residential services?
30 feet
Reference-: ESR, ESR-2 Figure 2-1
A clip-on ammeter reads 10 A on a 120 V conductor. What is the resistance?
R = E/I
R=120 V/ 10 A= 12 0hms
How much current would a 240 V heater, with 30 0 resistance, draw?
I= [,;-R I=240V-;-300 =8A
- lf a circuit has a total resistance of 20 0 and a current of 3 A, what is the voltage of the circuit?
E=lx R
E=6Ax200 =120V.
A 5000 W electric heating unit is supplied by a 240 V circuit. What is the current drawn by · the heater?
! =P+E
I =5000 W + 240 V =20.8 A
How is the total resistance in a series circuit calculated?
It is cumulative, i.e. Rr =R1+R2+R3 etc.
What is the full load (in amps} for a 100 kVA single-phase transformer with 120/240 V secondary service?
100,000 VA/ 240 V = 416.66 A
- A single-phase 120/240 Vcircuit is tested with a voltmeter and an ammeter with the following results: 240 Vand 200 A. At the time of measurement, the service meter measures 36 kW. What is the power factor?
36000/ 240 x 200 = .75
What is the full load for a 300 kVA three-phase transformer bank with 240 Vsecondaries?
VA
f = _£_x_1_7.-3 300,000 VA
l =240 vx 1.73 =722.5A
- What ls the main benefit and drawback of a radial distribution system?
Benefit: Cheapest and simplest Drawback: least reliable
What is the purpose of a distribution transformer?
Distribution transformers reduce primary voltages to secondary voltages to supply electrical service to customers
What are the different types of generating stations?
?
What is a “B” bank substation?
‘B” banks are SCE’s distribution transformers.
- List eight different types of “B” banks.
66/16 kV 66/12 kV 66/4 kV 33/12 kV 33/4 kV 16/4 kV 12/4 kV 12/2.4 kV
What must an employee do upon entering an attended substation?
- Report to the System Operator.
- Enter required informatiDn rn the Visitor Log.
- Provide System Operator with suitable contact information.
- Using the transformer diagram below, draw in the wiring for a three-phase, 3-wire - three- phase, 3 wire, ‘with a floating neutral, delta wye configuration.
?