What is the maximum distance that the base of an extension ladder must be placed out from a vertical wall that is 900 cm high?
300CM as Max. Min would be 225. 3:1 to 4:1 ratio
Can non-conductive, optical fibre cables used for industrial communications be run in the same raceway as a 480V electric power circuit?
Yes. Only for industrial applications 56-200(3)
Before closing the secondary of a delta transformer bank, a voltmeter indicates twice the rated voltage. Is this good?
No. It should read 0V. One transformer is wired backwards.
What is the smallest size available for neutral-support (NS90) cable?
8. Use table D1 (Page 533.) Don’t use table 36A or 36B. They will mislead you!
What is the maximum ampacity rating for four 1250 kcmil RW90XLPE aluminum conductors, when installed in a run of rigid metal conduit for a 3Ø, 4-wire feeder terminating on a circuit breaker?
485A. See 4-004,(2) b, (3), 4-006 (2), and Table 4.
Use T.2, 75° column…no de-rating for the neutral
The secondary circuits of instrument transformers, like this CT, should be grounded when the primary circuits are connected to ____ or more.
300V. See 10-116 (1)
What is the maximum voltage allowed between the conductors seen here in this unmarked surface raceway?
300V. Look up raceway surface index. 12-1608
What is the minimum size disconnect, shown here, for a 15 kVAR, 208V, single-phase, dry-type capacitor?
See 26-214
15000 VARs ÷ 208V = 72.1 FLC
72.1 amps x 135% = 97.35 amps..it will only fit into the next larger size disconnect.
Essentially, we size the disconnect to the fuse, if known, and at the very least the conductor size
What is the minimum number of straight threads that must be fully engaged in a rigid metal conduit threaded joint in a zone 21 hazardous location?
Note: The area contains Group IIB gasses.
See 12-1008.
Section 18 does not provide any special requirements for the number of threads, so we refer to the general section.
If replacing an ungrounded receptical with a grounded one. Can you ground to the cold water pipe?
Yes. 26-700(7)
If 120 VAC is placed across the input of this full wave bridge rectifier, what would be the expected DC output?
108V. 120VAC x .9 = 108
Medical electrical equipment is fed from an isolated system within a hospital.
What is the grounding requirement, if this equipment is permanently connected?
A conventional grounding system, installed in the separate raceway.
See 24-200(2)
What is the maximum distance that 1000 kcmil RW90XLPE aluminum conductors can be run unsupported in a raceway vertically in a shaft?
25M. See 12-120 & T.21
Explain how 3 light ground fault light indicators work fro 3 phase systems.
Will need to look this up.
What is the maximum rating of the overload relays that are used to protect this 25 hp, 575V, 3-phase refrigeration compressor, seen here?
37.8 Amps. See 28-710 (a) & T.44
FLA x 140% = max setting.
27 FLA x 1.4 =
Inserting more resistance in the starting controller of a wound rotor induction motor (WRIM) would:
The torque produced by an induction motor is function of stator flux, rotor current and rotor power factor.
By adding resistance at starting, the added resistance improves the rotor power factor and at the same time decreases the inrush current.
This gives high starting torque and reduced inrush amps.
A 3Ø, squirrel-cage motor is rated at 480 V, but is connected to a 600 V supply. What will happen?
Motor will run with 20% more power.
What is the full-load current rating of a 5 hp, 240VDC motor? What is the full-load current rating of a 5 hp, 240VDC motor?
20A. DC Motor FLA’s are found in Table D2
What is the torque formula?
T = (5252 x HP) ÷ N
T in lbs-ft
N in RPM
Why can’t you use a series excited DC motor on a belt drive?
Motor runaway will occur if belt breaks. Destroying motor.
What is the maximum size of non-time -delay (NTD) fuse that is permitted to protect a 50 kVA, 600- 120/208V, 3-phase, 4-wire liquid filled transformer?
80A. See 26-254 (2)a
50 000 VA ÷ (600V x √3) = 48.1 A primary
48.1 A x 150% = 72.2 A fuse…round up.
At what % of speed does a start split-phase motor should have its centrifugal switch open?
75%
Where pendant lamp holders are used the conductors must be twisted together when?
The conductors exceed 900 mm in length. See 22-104 (2) & 30-608(5)
A 3-phase, three-wire system has ground fault indicator lamps, all working properly.
What will happen if A-phase goes to ground?
A-phase light goes off.