Heat Trace Flashcards

1
Q

What are heat trace cables typically used for?

A

Prevention of freezing of liquids,
To melt snow and ice,
To maintain a specific temperature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the basic design principles of heat trace cable?

A

Series fixed resistance (Constant wattage),
Parallel fixed resistance (Constant wattage),
Self regulating variable resistance (Variating wattage),
Skin effect.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is used in MI cables as insulation?

A

A magnesium oxide powder or silicon dioxide powder.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Can you ever cut an MI heat trace cable to size?

A

No, as this will breach the seal. It is engineered for the job.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How far may polymer insulated series fixed resistance cables be run?

A

Up to 3500 m.

They are not practical for short runs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the large wires in a parallel fixed resistance heat trace cable called?

A

Bus conductors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is a power limiting cable?

A

A self regulating (by use of metallic alloy which changes resistance with temperature) parallel variable resistance heat trace cable.
May be used for higher temperatures than polymer self regulating cables.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When the carbon polymer shrinks in a self regulating cable, what is the effect?

A

More electrical connections are made and the heat output increases due to the physical response to a cold environment.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What principle does skin effect heat tracing rely upon?

A

That current will only flow on the inside shell of a ferromagnetic tube.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How far may one run of skin effect heat tracing be used?

A

15 km.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If current is too high, how should a thermostat control a heat trace cable?

A

By use of a contactor.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Why is solid state switching advantageous?

A

The lack of moving parts allows for mush greater durability under constant switching.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Why is soft starting used in heat trace systems with self regulating cable?

A

Because often the cold resistance is low enough to cause bad nuissance tripping. a lower voltage is applied as the cable heats up so that it can heat and not trip the breaker.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is average current control?

A

The pulsing of current through a self regulating cable to simulate a soft start, this is often mush easier to achieve than actually varying the voltage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Must heat trace circuits be protected by class A GFCI?

A

No, not necessarily the same level as class A, check section 62-116 and APP B. for more info.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Would a GFCI be used in a critical processing industrial plant?

A

No, simply an alarm circuit as the process should not have to be interrupted if there are trained personnel on site to handle the problem.

17
Q

When installing heat trace cable why must it be on the outside of the 90s?

A

Because that is where they lose the most heat.

18
Q

Must provisions be made for the removal of valves when running heat trace?

A

Yes, or the plumber may cut the wire.

19
Q

If using MI heat trace cable, how must it be attached to a pipe?

A

By metal banding.