Refrigeration Calculations and theory Flashcards
400 series zeotropic or azeotropic
zeotropic
400 series will or will not fractionate
Will
How many btu in 1 Ton of refrigeration
200/ min
12000/ hr
288000 /24hr
Formula for system capacity in BTU
Mass Flow Rate (lb/Min) x Net Refrigeration Effect (BTU/Lb)
Formula for Volumetric Flow Rate
Mass Flow Rate (lb/min) x Specific Volume (ft3/lb)
Density and specific volume relation ship
Inverse
1/SV = density
1/density = specific volume
Actual displacement formula
Theoretical displacement (CFM or ft3/min) x Volumetric efficiency%
Compression ratio formula
Discharge / suction pressure
IN ABSOLUTE!!!
Coefficient of performance formula
Net Refrigeration Effect / Heat of Compression
Condenser correction factor formula
CONDENSOR Heat of Rejection / Net Refrigeration Effect
Theoretical HP
Mass Flow Rate x Heat of Compression
—————————-
42.42
Required water flow for condensor formula
Q BTU/HR = 500 x GPM x Temperature change
Use condensor tonnage (found by using CCF)
Use 600 for imperial gallons
What is Approach
Temperature difference between Entering Air Wet bulb and leaving water dry bulb
What is reach
Difference in temp between entering water dry bulb and leaving water dry bulb