Pressure Control Ppt (Not on written exam) Flashcards
Pressure Controls:
A _______ sensing device used to measure or control the pressure of refrigerant, oil, air, gas, and, water
pressure
Pressure Controls: Components of pressure control; Pressure sensing element;
bellows
diaphragm
______ tube
bourden
Pressure Controls: Components of pressure control; connecting tube;
capillary tube
braided _____ hose
small diameter tubing (1/4” O.D.)
Electrical switch
Adjustment screws
metallic
Pressure Controls:
- used to switch electrical loads, such as a ________ motor
- Used to operate devices directly, such as ______
- compressor
2. valves
Pressure Controls: Pressure Control types and switching action;
- Low pressure control - ____ on a rise in press
- High pressure control - _____ on a rise in press
- Low ambient control- ____ on a rise in press
- oil pressure safety - Normally ____ pressure switch with a time delay circuit and the pressure switch opens on a rise of _________
- closes
- opens
- closes
- closed, differential
Pressure Controls: Operation of pressure controls;
Pressure sensing element moves as a change in pressure is sensed and mechanically opens or closes an ________ switch
- Switches are ____ acting
- Can operate over a wide range of ______
electrical
- snap
- pressures
Pressure Controls: Setting of pressure controls.
- Control range: the cut in pressure and cut out pressure
- Cut in: Point at which the control _____ the electrical circuit
- Cut out: point at which the control _____ the electrical circuit
- Differential: difference between the cut in and cut out pressure
- makes
3. opens
Low Pressure Control: Application;
- Used as a safety control to protect against ___ charge
- Used as temperature control, cycles compressor on _______ refrigerant temperature
- Used as a _____ down control and shuts down compressor after remote t-stat stops liquid flow
- low
- saturated
- pump down
Low pressure control:
- Operation: Closes on a rise in pressure. _______ and non adjustable types
- Settings:
Cut in : adjustment screw
Differential - cut out = cut in minus differential
Example:
-cut in 35 psig
- diff 5 psig
cutout = 35-5 = 30psig
adjustable
Low pressure control: Pump down system;
- Cut out: close to __ psig without going into vacuum
- Cut in: Max operating temp, convert to psig (for that refrigerant), divide by two
- 0
Low pressure Control: Example;
Pump down system:
- HFC 134A system temp range 38F to 40F
Cut-out close to 0psig
Cut-in HFC 134A 40F to Psig
35/2 = 17.5psig
correct example
Low Pressure Control: Used as a Temp Control:
Cut - in highest temperature/Pressure from operating range
formula*
Low Pressure Control: Used as a Temperature Control:
Cut in/Cut-out calculation:
1. Find coil pressure drop (Pd), take a suction pressure reading as the unit starts
- Take a second pressure reading as the compressor starts to work when the evaporator comes down to m
- Substract the difference. The difference will account for pressure drop across the evap
- Subtract PD from converted low end temp
formula
Low Pressure Control:
Note: If the pressure control has a range adjustment or a differential adjustment, the cut-in pressure must be set _____
If pressure control is equipped with a cut -in and a cut-out adjustments, either can be adjusted _____
first
first
Low Pressure Control: Example:
HFC 134A system operating range 35F - 40F
- Cut in 40F = 35Psig
- Cut out System starts at 35psig and comes down to 25psig, PD= 10
- 35F to pressure = 30psig - 10psig = 20psig (set point)
exmaple