Such sign shall have the letters “FDC” not less than____ (152 mm) high and words in letters not less than____ (51 mm)
high or an arrow to indicate the location.
6 inches / 2 inches
A working space of not less than ____ (914 mm) in width, ___ (914 mm) in depth and ____ (1981 mm) in
height shall be provided and maintained in front of and to the sides of wall-mounted fire department connections
36 inches / 36 inches / 78 inches
A metal sign with raised letters not ____ (25 mm) in size shall be mounted on all fire department
connections serving automatic sprinklers, standpipes or fire pump connections. Such signs shall read: AUTOMATIC
SPRINKLERS or STANDPIPES or TEST CONNECTION
less than 1 inch
The key box shall be mounted ____ (1676mm) above the finished floor to the right side of the
elevator bank.
5 feet 6 inches
All Fire Department sprinkler and standpipe inlet connections shall be provided with approved signs indicating the type of system and the
area served. Signs shall be securely attached to the building
adjacent to the inlet connections. Signs shall be not
less than_____.
8 inches (203 mm) in width and 4 inches (100 mm) in height
Exit sign placement shall be such that no point in an exit access corridor or
exit passageway is more than ____ (30 480 mm) or the listed viewing distance for the sign, whichever is less, from
the nearest visible exit sign.
100 feet
Fire control room/ Fire command center shall be not less than _____ in area with a minimum dimension of ____.
200 square feet / 10 feet
Portable fire extinguishers having
a gross weight not exceeding 40 pounds (18 kg) shall
be installed so that the top of the extinguisher is not more
than ____ above the floor.
5 feet (1524 mm)
Extinguishers having
a gross weight greater than 40 pounds (18 kg) (except
wheeled-type) shall be so installed that the top of the
extinguisher is not more than_____.
31/2 feet (1065 mm) above
the floor.
In no case shall the clearance between the bottom
of the extinguisher and the floor be less than_____
(100 cm).
4 inches
Portable fire extinguishers should
not be located where ambient temperatures exceed ____
(49°C). unless otherwise noted on the nameplate of the
extinguisher.
120°F
Extinguishers as specified in California Code of Regulations,
Title 19, Division 1, Section 568, Table 2 may be
replaced by uniformly spaced_____ by the occupants of the building.
11/2 inch (3.810 cm) hose
stations for use
Smoke alarms or smoke detectors shall be installed
a minimum of ____ horizontal distance from a permanently
installed cooking appliance.
20 feet
OCCUPANT LOAD
PER STORY = MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS FROM STORY
1-500
2
OCCUPANT LOAD
PER STORY = MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS FROM STORY
501-1000
3