EDG cards Flashcards
How many emergency diesel generators are there?
4,1A 1B 1C 1D
How many DG air dryers are there?
8, 2 air dryers per diesel
How many DG diesel fuel oil day tanks are there?
4, 1 day tank per diesel
What is the motive force used to start the DGs?
Air from the air receivers is used to start the diesel generators?
Question
Answer
How many emergency diesel generators are there?
4,1A 1B 1C 1D
How many DG air compressors are there?
8, 2 air compressors per diesel
How many DG air dryers are there?
8, 2 air dryers per diesel
How many DG diesel fuel oil day tanks are there?
4, 1 day tank per diesel
What is the motive force used to start the DGs?
Air from the air receivers is used to start the diesel generators.
What will auto start a DG?
DGs will auto start on an SI signal or a UV on an ESF bus.
How much time is a DG allowed to take to start?
A DG must be up to rated speed and voltage within 10 seconds.
How much time is a DG allowed to take to start?
A DG must be up to rated speed and voltage within 10 seconds.
What will trip a DG after an emergency start?
ONLY Overspeed, Generator differential current and the Emergency Stop pushbutton
What will trip a DG after an emergency start?
ONLY Overspeed, Generator differential current and the Emergency Stop pushbutton
What will trip a DG after a test mode start?
Overspeed, Generator Differential current, Emergency Stop Push Button, Overcurrent, Neutral Overcurrent, Reverse Power, Loss of Field, Underfrequency, Low Lube Oil Pressure, Low Turbocharger oil pressure, Turbocharger thrust bearing failure, High crank case pressure, main bearing high temperature, jacket water high temperature, connecting rod bearing temperature, generator bearing high temperature, incomplete starting sequence
What will trip a DG output breaker on an SI start?
ONLY Control room switch in Trip or PTL, output breaker 1413 differential current
What will trip a DG output breaker on a UV start?
Control room switch in Trip or PTL, Overcurrent, Ground overcurrent, reverse power, underfrequency, loss of field, output breaker 1413 differential current, lockout on 1412 (241 cross-tie breaker)