According to a regular preventative maintenance schedule which action should be done to a pneumatic piston actuator?
Replace the O-Rings
Which should be done to prevent the hydraulic piston from stroking?
Open the bypass valves
Communication driver has stopped on the HMI is the result?
Graphics freeze
What must be checked when replacing a defective load cell on a weigh scale?
Load rating and excitation voltage
What should be done when calibrating a filled thermal system?
Immersed bulb completely in bath
Which method is used to install a conditioned sample system on exhaust gases from a flue stack?
Use a small 1/4 inch or less diameter sample tube providing filtration upstream of an analyzer, and a vacuum pump located downstream of the analyzer
What should be done when modifying a computer program?
Back up original program, make changes, verify changes and save changes
A density is calibrated wet into a fluid with a specific gravity range of 0.7-1.2, what will have the greatest effect on the density calibration?
The temperature of the fluid used for calibration
Which steps are required when changing the flashing module of an enunciator panel?
Alert operator, change module, verify operation, file report
Which actuator is installed on a 4 inch globe valve?
Diaphragm reciprocating
An electronic weight measuring system uses a linear variable differential transformer (LVDT), output to indicate the weight of the can, what has to be done to recalibrate the instrument?
Recenter the core in the LVDT
A spring diaphragm actuator has stopped working on inspection it is found that the yoke and dome is badly corroded with nitric acid. What’s done to correct the problem?
Replace the actuator
Which diagram illustrates a functional start/stop PLC program with both the start and stop buttons are normally open (NO) momentary type?
C
What should be done if a spring diaphragm actuator does not provide the travel expected?
Check the spring
A hydrogen sulphide H2S gas detector has a range of 0-60ppm and an output range of 0-175mV. What would be the output voltage for an alarm point of 20ppm?
20ppm/60ppm=0.3333x175mV=58.3mV