Calcium chloride brine solutions are suitable for food processing applications because it uses simple table salt in mixture (t or f)
f
when using an electric float for the control of ammonia systems a needle valve must always be used to control the amount of liquid refrigerant entering the chiller, this valve is normally located up stream of the liquid solonoid valve (t or f)
t
calcium chloride may be stored in the same location or equipment room as ammonia as long as there is no direct source of heat (t or f)
f
copper or brass may be used in ammonia systems as long as there is no moisture present in the equipment room (t or f)
f
the minimum test pressure for the lowside of an air cooled ammonia system is equal to or greater than the setting of the pressure relief device (t or f)
f
cascade is desirable if system temperatures of lower than -125 are required
t
the liquid recirculating pump as used with 2 stage liquid recirculation ammonia systems is located between
The low pressure receiver and the evaporator
the boiling point of r717 at atmospheric pressure is
-28f
when installing globe valves in any system for component isolation how should they be installed on horizontal line rows
the stem should be at right angles to a horizontal run of pipe and the high pressure side exerted on the bottom side of seat assembly
what component is not normally required in cascade systems
low stage condenser
which type of intercooler is not suitable for ammonia compression systems
dry type
multi stage or booster compression systems are normally required for low temp applications such as ammonia blast freezers. This type of compression system is normally good for applications above -90f and should be used if the reciprocating compression ratio of a single stage system exceeds
10;1
multi stage compression systems can be put in 2 groups
cascade or direct
ammonia receiver 3ft x 60’’ long what is the prv capacity
7.5 lbs per min
the corrosiveness of a brine or eutectic mixture should be maintained between _ and _ and can be determined by a ph tester
7-8.5
the normal temp drop through a lower temp chiller is normally
2f at a flow rate of 10 to 15 gallons per ton